Technical Details - Pilz PSS DIO Z Mode D'emploi

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

PSS(1) DIO Z

Technical Details

Electrical Data
Supply Voltage
Tolerance Range
Galvanic Isolation
Polarity Protection
Connection
Outputs
Number
Potential Isolation
Status Indicator
Output Current at "1"-Signal
Total Load Capacity at +60 °C
Permitted Range
Short-Circuit Protection
Limitation of inductive switch-off
at the load
Simultaneity
Residual Current at "0"-Signal
Output Signal Level
"0"-Signal (low)
"1"-Signal (high)
Output Switch Delay
Switch-off Pulse
Inputs
Number
Potential Isolation
Input Signal Level
"1"-Signal (high)
"0"-Signal (low)
Input Current
Input Delay
Status Indicator
Environmental Data
Protection type (EN 60 529, 10/91)
6
24 V DC
20 ... 30 V DC including residual ripple
Yes (Optocoupler)
Yes
Screw-type connector, max. 2.5 mm
(AWG12)
8
Yes
One LED per output
2 A
10 A
0 ... 2.5 A
Electronic
-U
B
100 % up to max. 10 A
Test impulse: 5 mA for max. 700 µs
12 V DC both output terminals
U
... 2 V DC at 2.5 A
B
50 µs
< 700 µs
16
Yes
+15 ... +30 V DC
-3 ... +5 V DC
Average 6 mA
< 1 ms
One LED per input
IP 20 (installed on module rack)
2
Operating Manual