5-6. Wiring Input Power Connector (NEMA L16-20R)

3
1

5-7. Electrical Service Guide

Failure to follow these electrical service guide recommendations could create an electric shock or fire hazard. These recommenda-
tions are for a dedicated circuit sized for the rated output and duty cycle of the fume extractor.
In dedicated circuit installations, the National Electrical Code (NEC) allows the receptacle or conductor rating to be less than the rating
of the circuit protection device. All components of the circuit must be physically compatible. See NEC articles 210.21, 630.11, and
630.12.
Input Voltage (V)
Input Amperes (A) At Rated Output
Max Recommended Standard Fuse Rating In Amperes
Min Input Conductor Size In AWG
Max Recommended Input Conductor Length In Feet (Meters)
Min Grounding Conductor Size In AWG
Reference: 2011 National Electrical Code (NEC) (including article 630)
1 If a circuit breaker is used in place of a fuse, choose a circuit breaker with time-current curves comparable to the recommended fuse.
2 "Time-Delay" fuses are UL class "RK5" . See UL 248.
3 "Normal Operating" (general purpose - no intentional delay) fuses are UL class "K5" (up to and including 60 amps), and UL class "H" ( 65 amps and
above).
4 Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table
310.15(B)(16). If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table 400.5(A) for flexible cord and cable
requirements.
X Terminal
Y Terminal
1
2
Time-Delay Fuses
3
Normal Operating Fuses
4
4
2
Z Terminal
G Terminal
!
Installation must meet all Na-
tional and Local Codes − have
only qualified persons make
this installation.
1
Input Power Cord
Select cord according to Section 5-7.
2
480 V AC, Three-Phase, 20 A,
3P4W Connector (Supplied)
OR
600 V AC, Three-Phase, 30A
3P4W Connector (Supplied)
3
Cord Grip
Strip insulation from end of each wire
in cord and connect wires to connec-
tor as follows:
• Green Or Green/Yellow Wire To G
Terminal
• Black Wire To X Terminal
• White Wire To Y Terminal
• Red Wire To Z Terminal
Reinstall outer shell and cord grip.
Plug 5 2013 -06 261 487-A
Elec Serv 2011-08
60 Hz Three Phase
460
575
5.8
4.8
20
30
12
12
50
50
12
12