Setting of the electronics
Should changes to the factory settings be necessary
after the first commissioning, it can be done on the
electronics.
Shortened or extended combustion cycle
Since the operation of the stove is primarily dependent
on the downstream chimney, you have the possibility
of reacting to different chimney conditions by choosing
different control curves.
Control curve 1:
→ Extended combustion cycle
→ Use, for example, with increased chimney draught
→ Primary air shuts off after 10 minutes
→ Reduced secondary air supply
→ „Add fuel" signal if temperature drops below 200°C
Control curve 2:
→ Normal combustion cycle
→ Primary air shuts off after 15 minutes
→ „Add fuel" signal if temperature drops below 280°C
Control curve 3:
→ Reduced combustion cycle
→ Use for poor chimney draught
e.g. transition times with increased outside
temperatures
→ Primary air shuts off after 20 minutes
→ Increased secondary air supply
→ „Add fuel" signal if temperature drops below 280°C
Control curve 4:
→ Specific combustion cycle
→ Use with water appliances, Tolima PowerSystem
and stoves with admixed air mechanism
→ Primary air shuts off after 20 minutes
→ Increased secondary air supply
→ „Add fuel" signal if temperature drops below 200°C
Control curve 5:
→ Normal combustion cycle (factory setting)
→ Primary air shuts off after 15 minutes
→ „Add fuel" signal if temperature drops below 200°C
Furthermore, there is the possibility of setting the shut-
off time of the primary air in a range of 1 to 60 minutes
for the electronics in the operator menu.
26
The display of the electronics
During operation, the following parameters can be op-
tionally displayed. Selecting is done using the P or M
buttons.
● t1 → Fire chamber temperature → 380 (°C)
● S1 → Combustion air slide valve position → 100(%)
● It → Current room temperature→ 19 (°C)
● St → Desired room temperature → 22 (°C)
● S2 → Convection air slide valve position → 100(%)
Indicates automatic mode
→ Illuminates in intervals
Indicates manual mode
(see chapter "Manual air slide valve operation")
→ Illuminates in intervals
Indicates combustion air slide valve position is 100%
open
Indicates a fire chamber temperature of 380°C