Adjusting the refrigerant charge
For lengths over or under 7.5 m., the nominal
charge should be increased or decreased
by the grams indicated in the corresponding
table, depending upon whether the length
of the liquid line has been increased or
decreased.
Check to see whether the refrigerant is cor-
rect by measuring overheating. In normal
summer conditions between 5 and 10° K
is correct.
Checking for leaks
Once the charging through the 1/4" nozzles
located in the circuit is complete, check for
leaks.
Application of R-410A refrigerant
Due to the characteristics of the refrigerant,

Physical data

Indoor units
Model
Nominal power
Power supply
Degree of protection
Indoor fan
Motor rpm
Turbine diameter
Turbine width
Amount
Pipes depth x height
Indoor coil
Pipe diameter
Surface
Amount
EU3 filters
Dimensions
Height
Dimensions
Width
with packing
Depth
Nett
Approximate
weight
Gross
12
its evaporation, condensation and discharge
temperature, its high operating pressure
in the units, and the specific requirements
needed for efficient operation (free of humid-
ity and dirt), it is obligatory to have a special-
ized group of technicians, with a certificate
of aptitude, handle the refrigerant.
Wiring

Electrical connections

The established national regulations must
be followed at all times.
Connection of the indoor fan
VIR 25A to 90A
Should the phase sequence (R-S-T) be cor-
rect but the indoor fan turns in the opposite
direction, interchange two phases at the
VIR 25A
VIR 40A
kW
0.75
V.ph.Hz
IP
mm
320
320 (x 2)
mm
320
240 (x 2)
1
4 x 21
0.57
3
365 x 543 x 24
447 x 616 x 24
mm
760
mm
1 470
mm
1 020
kg
128
kg
152
VIR 45A
1.5
1.5
400.3.50
55
1 400
320 (x 2)
320 (x 2)
1
1
4 x 25
4 x 29
3/8"
0.84
1.40
3
3
640 x 715 x 24
825
925
1 850
2 350
1 020
1 020
173
223
198
250
GB
bottom of the fan contactor.
Warning
Loose cables can cause overheat-
ing of terminals or incorrect opera-
tion of the unit. Fire hazards may
also exist. Therefore, make sure all cables
are connected tightly.
Do not power or operate the unit until all
pipes and electrical connections are made.
Make sure the power supply is connected
correctly to the units, as shown in the wiring
diagrams.
VIR 60A
VIR 75A
2.2
3
320 (x 2)
380 (x 2)
320 (x 2)
380 (x 2)
1
1
4 x 29
5 x 32
1.40
1.76
547 x 789 x 24
925
1 000
2 350
2 760
1 020
1 120
223
310
250
340
VIR 90A
4
380 (x 2)
380 (x 2)
1
5 x 32
1.76
3
1 000
2 760
1 120
312
342

Publicité

Table des Matières
loading

Table des Matières