Associated outputs
If required, select other control outputs associated to the zone. The address zone will be the one with a lower value.
Other settings
Configure other functionalities of the LITE thermostat from the advanced configuration menu of a Blueface thermostat (see
section Advanced Settings, Zone parameters).
If the association is correct, the icon
flashes red twice, it means the thermostat is out of range.
Remember: If you need to change the zone number, reset the thermostat and start association process.
Lite thermostat reset
If you want to return your Lite thermostat to factory values, pull down all the microswitchs and reinsert the thermostat in its
base. The icon
will flash green twice when the reset process is completed.
INITIAL CONFIGURATION EVALUATION
Check the following aspects:
-
AC unit-system communication: choose any mode (except STOP mode) and switch on the zone to generate demand.
Verify that the selected operation mode in the Master thermostat is shown in the indoor unit thermostat and the set-
point temperature changes.
-
AC unit-system communication: configure the Airzone system in stop mode and verify that the machine turns off and
the dampers open.
-
Opening-closing of the dampers and control outputs: Turn on the system and generate demand in all the zones. Then,
switch off and on all the zones to verify the associated control outputs are correct.
-
Verify that the static pressure of the duct system complies with the air distribution network conditions where is
installed (check the Manufacturer's Manual of the equipment if you need to modify this parameter).
Remember: For security reasons, the last zones takes 4 minutes to close.
FLOW REGULATION
Important: Start adjusting the flow from the central dampers and finish off with damper 1.