Do not place the system bus close to lines of force, fluorescent lights, LED lamps, motors, etc. It might cause
EN
interference on the communications.
•
Respect the connection polarity of each device. A wrong connection may seriously damage the product.
FR
•
For elements externally powered at 110 /230 Vac, for the communications, it is only necessary to connect the poles "A"
and "B" of the bus.
IT
•
For elements externally powered at 110/230 Vac, respect the connection polarity. A wrong grounding may produce
electric shocks.
PT
•
According to the current local and national regulations, it is mandatory to add a switch (or other element to disconnect
the system) to the external supply wiring so that a constant separation between poles is guaranteed. The system will
DE
restart automatically if the supply is eventually turned off. Use an independent circuit from the controlled system
for the power supply.
•
Once the Airzone system is configured, verify that the static pressure of the duct system complies with the air
distribution network conditions where is installed (check the Manufacturer's Manual of the equipment if you need to
modify this parameter).
INTRODUCTION
Airzone systems enable the management of Master and Zone interfaces. Master thermostats enable mode management or
define the efficiency level with the Eco-Adapt function.
It is recommended to use of a Blueface thermostat as Master Interface, this enables time schedule management and more
unique functionalities.
Remember: This system has to admits one Master thermostat.
To distinguish a Master Interface from a Zone Interface, check the next points:
-
Blueface Master: Mode, Eco-Adapt and Speed* icons shown in white color.
-
Blueface Zone: Mode, Eco-Adapt and Speed* icons shown in gray color.
-
Think Master: Accessing the settings menu, Operation mode and Speed* are available.
-
Think Zone: Accessing the settings menu, Operation mode and Speed* are unavailable.
*Note: Only available in installations with Fancoil.