Electric Connections; Connecting The Power Plug; Connecting The Multiple Switch; Connecting The Ebus Connector - ubbink Ubiflux W180 Consignes D'installation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Installation
5.5

Electric connections

5.5.1 Connecting the power plug

The appliance can be connected to an easily accessible,
earthed wall socket with the plug that is mounted to the ap-
pliance. The electric installation must comply with the require-
ments of your power company.
Make allowance for a 1000 W preheater/postheater that
may optionally be connected.

5.5.2 Connecting the multiple switch

The multiple switch (not supplied with the appliance) is con-
nected to the modular connector type RJ12 (connected to X2
on the control board) that is placed at the top of the appliance.
Dependent on the type of multiple switch that is used, a plug
RJ11 or RJ12 can be connected to it.
Application of a multiple switch with filter indication in all
cases requires an RJ12 plug in combination with a 6-core
modular cable.
Application of a 3-way switch without filter indication in all
cases requires an RJ11 plug in combination with a 4-core
modular cable.
Refer to diagrams §11.2.1 to §11.2.4 for connection examples
multiple switch.
Other options include wireless remote control or a combination
of multiple switches.

5.5.3 Connecting the eBus connector

The Ubiflux uses the eBus protocol. The 2-pole - detachable
- screw connector for the eBus connection is at the top of the
appliance.
The eBus protocol may for instance be used to connect (the
cascade control of) appliances (see §11.3). Because of polarity
sensitivity, always connect contacts X1-1 to X1-1 and contacts
X1-2 to X1-2; the appliance will not work when these contacts
are interchanged!
Ubiflux W180 / W180+
Chapter 5
Warning
The fans and control board carry a high volta-
ge. Always take the voltage from the appliance
by pulling the power plug when working on the
appliance.
modular connector
2-pole connector
13

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Ubiflux w180+

Table des Matières