Chapter 11
11.8 Connection example geo-heat exchanger (only possible for the Ubiflux+)
30 °C
Ⅱ
B
25 °C
Ⅱ
15 °C
10 °C
Ⅱ
A
3 °C
0 °C
Ⅱ
34
Electric connections accessories
Ⅰ
Ⅲ
Ⅳ
Ⅳ
Ⅰ
Ⅲ
Ⅳ
Ⅳ
Ⅰ
Ⅲ
Ⅳ
Ⅳ
Ⅰ
Ⅲ
Ⅳ
Ⅳ
Ubiflux W180 / W180+
A geo-heat exchanger can be connected to the
Ubiflux+.
The geo-heat exchanger can be connected to con-
nection no. 5 (GND), no. 6 (24V) and no. 9 (0-10V)
of 9-pole connector; this 9-pole connector is directly
accessible at the top of the appliance. Connect the
outside temperature sensor on 7 and 8 of the 9-pole
connector.
When the geo-heat exchanger is connected, it is
no longer possible to connect a postheater to the
Ubiflux+!
A = Minimum temperature
B = Maximum temperature
I = To dwelling
II = To atmosphere
III = From dwelling
IV = From atmosphere
When using a geo-heat exchanger, step number 27
must be changed from "OFF" to "ON". When the
air is routed through the geo-heat exchanger, the
Ubiflux+ display shows the text "EWT".
Step
Factory
Description
no.
setting
Switching on geo-
27
heat exchanger
Minimum tempe-
28
rature geo-heat
exchanger
Maximum tempe-
29
rature geo-heat
exchanger
Range
ON =
Switched on
OFF
OFF =
Switched off
5 °C
0 - 10°C
25 °C
15 - 40°C