G
B
The dead-man operation is only an emergency operation which must be activated
for a very short period and with the complete installation at sight so to have a
secure and safe control of the system. As soon as possible however, the failing
safety devices must be repaired and activated.
FLASHING LIGHT
Connect the flashing light to J7 flashing light outputs, use flashing lights ACG7059 and bulbs
of 40W maximum.
NB: This electronic K board can only supply power to FLASHING LIGHTS with inbuilt flashing
circuit.
PRE-FLASHING function
The DIP 5 in the ON position enables the pre-flashing, the FLASHING LIGHT and BUZZER
starts working 3 seconds before every movement of the gate.
The DIP 5 in the OFF position disables any pre-flashing, the FLASHING LIGHT, the BUZZER
and the motor will start at the same time.
BUZZER (COM.+ BUZZER-)
The current supplied to the Buzzer will be 200 mA at 24Vdc.
During the normal operation of the gate, opening and closing, the buzzer will buzz
intermittently. Only during the alarm situations (safety strip) the buzzing will almost be
constant.
GATE OPEN INDICATOR (A negativo - LSC)
It is turned ON when the gate is open or partially open, it is turned OFF only when the gate
is completely closed.
N.B.: connect in series to the indicator a resistance of 2K2. WE RECOMMEND NOT TO
OVERLOAD THE INDICATORS OUTPUT OTHERWISE THE GATE FUNCTIONING COULD BE
COMPROMISED OR THE CONTROL BOARD COULD BE DAMAGED.
TROUBLESHOOTING
After having carried out all connections, by carefully following the layout and having
positioned the gate in intermediate position, check the correct ignition of LEDS DL3, DL4,
DL7, DL8.
In case of no ignition of the LEDS, always with gate in intermediate position, check the
following and replace any faulty components.
DL3
switched off
Faulty opening limit switch
FAULT
After having carried out the various connections and having supplied
voltage, all the LEDS are switched off.
The motor opens and closes, but it has no strength and moves slowly.
The gate opens but does not close after the time set.
The gate does not open or close by activating the various K and RADIO
buttons.
By activating the K button the gate does not move.
The slowing phase is not performed.
FINAL OPERATION
The gasket shall be fitted only at the end of the installation, before you mount the case.
Fit the gasket
TECHNICAL SPECIFICATIONS
Humidity
Power supply voltage
Frequency
Interruptions in electricity supply
Maximum load of motor outputs
Maximum load of blinker output with resistive load 40W
Maximum control board absorption (without accessories)
Current available for photocells and accessories
IP protection grade
Control board weight
Dimensions
TECHNICAL RADIO SPECIFICATIONS (model CRX)
Reception frequency
Impedance
Sensitivity
Time of excitation
Time of discharge
Memory available
Maximum load of radio receiver output
- All inputs shall be used as clean contacts without earthing, because the power supply is
generated in the card and is structured in such a way to guarantee the respect of double
and reinforced insulation to the elements under voltage
- All inputs are managed by a programmed circuit that carries out a self-control every time
the gate is operated.
DL4
DL7
DL8
jumper between COM and EDGE)
During functioning with personnel present, with DIP 1 at ON, check that during opening the
green DL6 LED switches on and that during closing the red DL5 LED switches on.
If not, invert clamps V and W on the motor terminal board.
Check the integrity of fuses F1 and F2.
In case of interrupted fuse use only of adequate value
Check trimmers TORQUE and LOW-SPEED adjustment.
Ensure to have set DIP 3 at ON. Button K BUTTON always inserted in automatic functioning mode (DIP 6 OFF).
Replace button or switch of the selector switch.
Failed edge self-test => check the connections between electronic board and edge feeder.
Attention: if not using a feeder for edges, DIP 10 must be at OFF position.
Faulty safety edge contact. Faulty photocells contact with DIP 4 OFF.
Fix or replace the relative contact.
Impulse K always inserted. Check and replace any buttons or micro-switches of the selector switch.
Ensure that DIP 8 is at position OFF (slowing enabled).
Learn the times through procedure from DIP 2.
Check trimmer LOW-SPEED adjustment.
The gasket is fitted
32
switched off
Faulty closing limit switch
switched off
Faulty photocells
switched off
Faulty safety edge (In case the edge is not connected, carry out
SOLUTION
F2 = 5A
F1 = 100mA.
Close the case
< 95% without condensation
230V~ ±10% (120V/60Hz upon
request)
50/60 Hz
20ms
1CV
33 mA
0,4A±15% 24Vdc
IP54
0,55 kg
130 x 50 x 115 mm
433,92 MHz
52 OHM
>2,24µV
300ms
300ms
60 codes (30 for complete opening
and 30 for pedestrian opening)
200mA 24Vdc
Motor ready