POINT A -
ELECTRIC CONNECTIONS
J1
DO NOT REMOVE ANY JUMPER! OTHERWISE THE
OPERATOR WILL NOT WORK!
J2
AERIAL
Radio Antenna
LSC
Close limit-switch that cuts off the motor in closing
LSO
Open limit-switch that cuts off the motor in opening
COM
Limit-switch common contact
PED BUTT
Pedestrian opening contact (NO)
J3
L-N
Main power supply 230 Vac 50/60 Hz (120V/60Hz upon
request)
J4
EARTH
Connection of the earth line
J5
RADIO
Built-in radio module (model CRX),
or connector for radio receiver RIB, 24Vdc supply
J6
A+ TEST
24Vdc safety strip self-test power supply
A+
Accessories power supply +24Vdc
A-
Accessories power supply -24Vdc
COM +
Common contact (common line for all the command and
safety inputs) (+)
K BUTT.
Single pulse contact (NO)
PHOT.
Photocells contact (NC)
EDGE
Safety strip contact (NC)
Buzzer contact (24Vdc max 200 mA) (-)
-
J7
Flashing light (max 40W )
U - MOTOR
Motor common connection
V-W -
Motor phase and capacitor connections
MOTOR
J8
PROBE
Temperature sensor cable connection PROBE (Code
ACG4665 optional)
RELAYS AND MOTOR COMMAND
K1 => Flashing light command
K2 => Closing command
K3 => Opening command
Q1 => TRIAC - Motor command in opening and closing
POINT B - SETTINGS
DIP 1 MOTOR ROTATION DIRECTION CHECK (See Point C)
DIP 2 PROGRAMMING (See Point D)
DIP 2-1 PROGRAMMING OF THE PEDESTRIAN OPENING (See Point D)
DIP 1-2 STORAGE/DELETION OF RADIO CODES FOR COMPLETE OPENING (DIP 1 ON
followed by DIP 2 ON) (POINT F) ONLY FOR CRX MODELS
DIP 1-3 STORAGE/DELETION OF RADIO CODES FOR PEDESTRIAN OPENING (DIP 1 ON
followed by DIP 3 ON) (POINT G) ONLY FOR CRX MODELS
OPERATING MODE SETTINGS
DIP 3 ON - Automatic Closing ENABLED
OFF - Automatic Closing DISABLED
DIP 4 ON - Photocells active only in closing
OFF - Photocells always active
DIP 5 ON - blinker pre-flashing
OFF - blinker normal-flashing
DIP 6 ON - STEP BY STEP (OPEN-STOP-CLOSE-STOP-OPEN...)
OFF - AUTOMATIC
Single pulse contact (K BUTT)
Pedestrian button (PED BUTT)
Radio Receiver command
DIP 7 ON - electronic brake ENABLED
OFF - electronic brake DISABLED
With K FCM it is mandatory to activate the electronic brake - DIP 7 on ON mode
DIP 8 ON - low speed in approaching DISABLED
R1
R2
J1
R1
TRIMMER
Electronic regulator for low speed on approach
LOW
SPEED
R2
TRIMMER
Electronic torque regulator
TORQUE
OFF - low speed in approaching ENABLED
DIP 9 ON - gradual start ENABLED
OFF - gradual start DISABLED
DIP 10 ON - safety strip self-test ENABLED
OFF - safety strip self-test DISABLED
DIP 11 OFF
DIP 12 OFF for K800-K1400
ON for K2200
S1 => PROG. Programming button
TORQUE => R1 Electronic regulator for motor torque
Adjustment of motor torque is carried out using the TORQUE Trimmer which varies the output
voltage to the head/s of the motor/s (turn clockwise to increase torque).
This torque control is activated after 2 seconds form any manoeuvre begging, whereas the
motor is turned on at full power to guarantee the starting at the manoeuvre begging.
PAY ATTENTION: IF THE TORQUE TRIMMER SETTING IS CHANGED, IT IS PREFERABLE
TO REPEAT THE TIME PROGRAMMING.
LOW SPEED => R1 Electronic regulator for low speed on approach
Adjustment of low speed is carried out using the LOW SPEED Trimmer which varies the output
voltage to the head/s of the motor/s (turn clockwise to increase speed). Adjustment is carried
out to establish the correct speed at the completion of opening and closing, depending on the
structure of the gate, or if there is any light friction that could compromise the correct working
of the system. The low speed is activated (DIP8 OFF) when the gate leaf is 0.50-0.60 meters
away from the complete close or open position.
ELECTRONIC BRAKE
With K FCM it is mandatory to activate the electronic brake - DIP 7 on ON mode
If the low speed in approaching is disabled (DIP8 ON), is preferable turn the DIP7 ON to enable
at least the electronic brake that permits to win the gate leaf inertia when the gate reaches
29
J3
J4
J7
J6
J8
J2
J5