Wired Controller XK46
Parameter
Parameter name
code
Set quantity of
P14
group control
indoor units
Set unit of
P16
temperature
Set static pressure
P30
of indoor fan motor
High ceiling
P31
installation*
P33
Set Timer
Parameter
range
00: forbid this
function
01-16: indoor unit
quantity
00:Celsius
01:Fahrenheit
01-09: static pressure
level of indoor fan
motor
00: installation height
of standard ceiling
01: installation height
of high ceiling
00: general timer
01: clock timer
28
Default
Note
value
Set the corresponding value
01
according to the connected
indoor unit quantity.
00
There are two kinds of static
pressure level:
5 levels: 03, 04, 05, 06, 07
9 levels: 01, 02, 03, 04, 05,
06, 07, 08, 09
Wired controller can be
adapted to the different types
of indoor units that it
possesses 1-9 level selection
05
for setting static pressure.
When the indoor unit with 5
static pressure levels
received the level setting
sent by wired controller is
less than 3, it will be settled
as the 3rd level; if it is over 7,
it will be settled as the 7th
level.
Only applicable to cassette
00
units
00
--
--