Wiring
A+:
AS-i +
A-:
AS-i -
I1-1/I1-2
I2-1/I2-2: switching input mechanical
contact I1 / I2
LEDs 1:
switching status indication
inputs I1, I2
LEDs 2:
AS-i, FAULT
X1-X2:
external LED output
Data bits
Data bit
In/Out
Addressing
When mounted and wired the PCB can be addressed via the address-
ing unit AC1144 using the cable (E70032).
Assign a free address between 1A/1B and 31A/31B. At the factory the
address is set to 0.
If a slave with the extended addressing mode is used in combination
with a master of the first generation (version 2.0), the parameter P3
must be 1 and the output bit D3 must be 0*. The output bit D3 and
the parameter bit P3 must not be used.
If a slave with the extended addressing mode is used in combination
with a master of the first generation (version 2.0), an address between
1A and 31A must be assigned to this slave.
6
D0
D1
I-1/O-1
I-2
D2
D3
-
-
*
Default setting