Framing And Clearances; Clearance To Sprinkler - Kozy Heat Fireplaces KZK-1510A Manuel D'installation

Komfort zone kit for use with the bhm-44 and clw-50
Masquer les pouces Voir aussi pour KZK-1510A:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

2.0 FRAMING AND CLEARANCES

2.1 Clearance to Sprinkler

In a situation where a sprinkler head is installed within the
proximity to a #KZK discharge opening, the diagram below
MUST be followed.
The distance between a sprinkler head and discharge opening
cannot be less than 60" (1524mm) in length at every point from
the origin of the discharge opening. You must also verify the
sprinkler head sensor is set to the proper heat setting so it does
not activate when the room heats up from the fireplace being
operated normally.
Please follow local building codes to determine what
temperature setting is relevant for your installation.
Figure 2.1, KZK Clearance to Sprinkler
8 FRAMING AND CLEARANCES
60"
(1524mm) MIN
Ceiling
sprinkler head
60"
(1524mm) MIN
Ceiling
sprinkler head
Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces
CLW-50
½
3
"
(89mm) MIN
BHM-44
3"
(76mm) MIN
Komfort Zone Kit #KZK-1510A R.4

Publicité

Chapitres

Table des Matières
loading

Table des Matières