SPECIAL PRECAUTIONS / SI (METRIC) CONVERSION FACTORS / UNIT LOCATION
CAUTION
17. In garages or other sections of aircraft hangars such
as offices and shops that communicate with areas used for
servicing or storage, keep the bottom of the unit at least
7 feet above the floor unless the unit is properly guarded
to provide user protection from moving parts. In parking
garages, the unit must be installed in accordance with
the standard for parking structures ANSI/NFPA 88A, and
in repair garages the standard for repair garages NFPA
#88B. In Canada, installation of heaters in airplane
hangars must be in accordance with the requirements
of the enforcing authority, and in public garages in
accordance with the current CSA B149.1 codes.
18. Low profile heaters are designed for use in heating.
applications with ambient temperatures between -40°F
and 90°F.
19. All literature shipped with this unit should be kept for
future use for servicing or service diagnostics. Do not
discard any literature shipped with this unit.
20. Ensure that the supply voltage to the appliance, as
indicated on the serial plate, is not 5% less than the rated
voltage.
21. Do not attach ductwork, air filters, or polytubes to any
propeller unit heater.
IMPORTANT
1. To prevent premature heat exchanger failure, do not locate
ANY gas-fired appliances in areas where corrosive vapors
(i.e. chlorinated, halogenated or acid) are present in the
atmosphere.
2. To prevent premature heat exchanger failure, the input to
the appliance as indicated on the serial plate, must not
exceed the rated input by more then 5%.
SI (METRIC) CONVERSION FACTORS
Table 3.1
To Convert
Multiply By To Obtain
"W.C.
0.24
kPa
psig
6.893
kPa
°F
(°F-32) x 0.555
°C
inches
25.4
mm
feet
0.305
meters
3
CFM
0.028
m
/min
GENERAL
CAUTION
1. All literature shipped with this unit should be kept for future
use for servicing or service diagnostics. Do not discard
any literature shipped with this unit.
2. Consult piping, electrical, and venting instructions in this
manual before final installation.
3. Do not attach ductwork, air filters, or polytubes to any
propeller unit heater.
In the U.S., the installation of these units must comply with the
"National Fuel Gas Code," ANSI Z223.1, latest edition (also
known as NFPA 54) and other applicable local building codes.
In Canada, the installation of these units must comply with local
plumbing or waste water codes and other applicable codes and
with the current code CSA B149.1.
1.
All installation and service of these units must be
performed by a qualified installation and service agency
only as defined in ANSI Z223.1, latest edition or in Canada
by a licensed gas fitter.
To Convert Multiply By To Obtain
3
CFH
1.699
m
/min
3
3
Btu/ft
0.0374
mJ/m
pound
0.453
kg
Btu/hr
0.000293
kW/hr
gallons
3.785
liters
psig
27.7
"W.C.
2.
This unit is certified with the controls furnished. For
replacements parts, please order according to the
replacement parts list on serial plate. Always know your
model and serial numbers. The right is reserved to
substitute other authorized controls as replacements.
3.
Unit is balanced for correct performance. Do not alter fan
or operate motors at reduced speed.
4.
Information on controls is supplied separately.
5.
The same burner is used for natural and propane gas.
UNIT LOCATION
DANGER
Appliances must not be installed where they may be exposed
to a potentially explosive or flammable atmosphere.
CAUTION
1. Low profile heaters are designed for use in heating
applications with ambient temperatures between -40°F
and 90° F.
2. Do not install unit outdoors.
3. In garages or other sections of aircraft hangars such
as offices and shops that communicate with areas used for
servicing or storage, keep the bottom of the unit at least
7 feet above the floor unless the unit is properly guarded
to provide user protection from moving parts. In parking
garages, the unit must be installed in accordance with
the standard for parking structures ANSI/NFPA 88A, and
in repair garages the standard for repair garages NFPA
#88B. In Canada, installation of heaters in airplane
hangars must be in accordance with the requirements
of the enforcing authority, and in public garages in
accordance with the current CSA B149.1 codes.
4. In aircraft hangars, keep the bottom of the unit at least
10' from the highest surface of the wings or engine
enclosure of the highest aircraft housed in the hangars
and in accordance with the requirements of the enforcing
authority and/or NFPA 409-latest edition.
5. Installation of units in high humidity or salt water
atmospheres will cause accelerated corrosion resulting in
a reduction of the normal life of the units.
IMPORTANT
To prevent premature heat exchanger failure, do not locate
ANY gas-fired appliances in areas where corrosive vapors
(i.e. chlorinated, halogenated or acid) are present in the
atmosphere.
Location Recommendations
1. When locating the furnace, consider general space and
heating requirements, availability of gas and electrical
supply, and proximity to vent locations.
2. When locating units, it is important to consider that the
combustion air and exhaust vent piping must be connected
to the outside atmosphere. Vent terminals should be located
adjacent to one another. Maximum equivalent vent lengths
are listed in table 5.1 on page 5.
3. Be sure the structural support at the unit location site is
adequate to support the weight of the unit. For proper
operation the unit must be installed in a level horizontal
position.
4. Do not install units in locations where the flue products
can be drawn into the adjacent building openings such as
windows, fresh air intakes, etc.
3 3