INSTALLATION

Gas Connections

WARNING
1. All field gas piping must be pressure/leak tested prior to
operation. Never use an open flame. Use a soap solution
or equilavent for testing.
2. Gas pressure to appliance controls must never exceed 14"
W.C. (1/2 psi).
3. To reduce the opportunity for condensation, the minimum
sea level input to the appliance, as indicated on the serial
plate, must not be less than 5% below the rated input, or 5%
below the minimum rated input of duel rated units.
CAUTION
1. Purging of air from gas lines should be performed as
described in ANSI Z223.1 - latest edition "National Fuel
Gas Code", or in Canada CSA B149.1 codes.
2. When leak testing the gas supply piping system, the
appliance and its combination gas control must be isolated
during any pressure testing in excess of 14" W.C. (1/2 psi).
3. The unit should be isolated from the gas supply piping
system by closing its field installed manual shut-off
valve.This manual shut-off valve should be located within
6' of the heater.
4. Turn off all gas before installing appliance.
IMPORTANT
To prevent premature heat exchanger failure, the input to the
appliance, as indicated on the serial plate, must not exceed
the rated input by more than 5%.
1.
Installation of piping must conform with local building codes,
or in the absence of local codes, with the National Fuel Gas
Code, ANSI Z223.1 (NFPA 54) - latest Edition. In Canada,
installation must be in accordance with CSA 149.1.
2.
Piping to units should conform with local and national
requirements for type and volume of gas handled, and
pressure drop allowed in the line.Refer to Table 13.1 to
determine the cubic feet per hour (CFH) for the type of gas
and size of unit to be installed. Using this CFH value and
Table 9.1
Gas Pipe Capacities
Gas Pipe Capacities (Up to 14 W.C. Gas Pressure through Schedule 40 Pipe)
Length
of Pipe
1/2"
(feet)
Natural
Propane
10
132
83
20
92
58
30
73
46
40
63
40
50
56
35
60
50
32
70
46
29
80
43
27
100
38
24
125
34
21
150
31
20
Cubic Feet per Hour with Pressure Drop of 0.3 W.C.
Natural Gas - Specific Gravity - 0.60
Propane Gas - Specific Gravity - 1.50
3/4"
Natural
Propane
Natural
278
175
520
190
120
350
152
96
285
130
82
245
115
82
215
105
66
195
96
60
180
90
57
170
79
50
150
72
45
130
64
40
120
the length of pipe necessary, determine the pipe diameter
from Table 9.1. Where several units are served by the
same main, the total capacity, CFH and length of main must
be considered. Avoid pipe sizes smaller than 1/2". Table
9.1 allows for a 0.3" W.C. pressure drop in the supply
pressure from the building main to the unit. The inlet
pressure to the unit must be 6-7" W.C. for natural gas and
11-14" W.C. for propane gas. When sizing the inlet gas pipe
diameter, make sure that the unit supply pressure can be
met after the 0.3" W.C. has been subtracted. If the 0.3"
W.C. pressure drop is too high, refer to the Gas Engineer's
Handbook for other gas pipe capacities.
3.
Install a ground joint union with brass seat and a manual
shut-off valve adjacent to the unit for emergency shut-off
and easy servicing of controls, including a 1/8" NPT
plugged tapping accessible for test gauge connection
(See Figure 9.1). Verify the manual shut-off valve is
gas tight on an anual basis.
4.
Provide a sediment trap before each unit in the line where
low spots cannot be avoided. (See Figure 9.1).
5.
When Pressure/Leak testing, pressures above 14" W.C.
(1/2 psi), close the field installed shut-off valve, disconnect
the appliance and its combination gas control from the
gas supply line, and plug the supply line before testing.
When testing pressures 14" W.C. (1/2 psi) or below, close
the manual shut-off valve on the appliance before testing.
Figure 9.1
Recommended Sediment Trap/Manual Shut-off Valve
Installation - Side or Bottom Gas Connection
SUPPLY LINE
GAS
SUPPLY LINE
3"
MIN.
Manual shut-off valve is in the "OFF" position when handle is perpendicular to pipe.
Pipe Diameter
1"
1-1/4"
Propane
Natural
Propane
328
1050
662
221
730
460
180
590
372
154
500
315
135
440
277
123
400
252
113
370
233
107
350
221
95
305
192
82
275
173
76
250
158
GAS
GROUND
MANUAL
JOINT
SHUT-OFF
UNION
VALVE
CONTROLS
PLUGGED
1/8" NPT TEST
GAGE CONNECTION
SEDIMENT
TRAP
1-1/2"
Natural
Propane
Natural
1600
1008
3050
1100
693
2100
890
561
1650
760
479
1450
670
422
1270
610
384
1150
560
353
1050
530
334
930
460
290
870
410
258
780
380
239
710
TO
2"
Propane
1922
1323
1040
914
800
725
662
586
548
491
447
9