Connection Terminals; Notes; Technical Data - DOLD SAFEMASTER BH 5928 Manuel D'utilisation

Modules d'arrêt d'urgence avec temporisation
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Connection Terminals

Terminal designation
A1(+)
A2 (-)
S12, S14, S22, S31, S32, S34, Y39 Inputs
S11, S13, S21, S33, Y40
13, 14, 23, 24, 33, 34
37, 38, 47, 48, 57, 58, 67, 68
31, 32, 41, 42

Notes

To select automatic restart terminals S13 - S14 must be bridged, S33 -
S34 must be opened. Open terminals S13 - S14 select manual restart, the
On-button must then be connected to S33 - S34.
Line fault detection on On-button:
The line fault detection is only active when the time delayed relais K1
and K2
have released and then S12 (channel A) and S32 (channel B)
t
are switched simultaneously. If the On-button is closed before S12, S31,
S32 is connected to voltage (also when line fault across On-button), the
output contacts will not close. The unit will not restart before the time delay
is finished.
A line fault across the On-button which occurred after activation of the
relay, will be detected with the next activation and the output contacts will
not close. If a line fault occurs after the voltage has been connected to
S12, S31, S32, the unit will be activated because this line fault is similar
to the normal On-function.
The unit can be operated with single channel and 2-channel operation
with cross fault monitoring. For connection please refer to application ex-
amples.
The gold plated contacts of the BH 5928 mean that this module is also
suitable for switching small loads of 1 mVA - 7 VA, 1 mW - 7 W in the range
0.1 - 60 V, 1 - 300 mA. The contacts also permit the maximum switching
current. However since the gold plating will be burnt off at this current
level, the device is no longer suitable for switching small loads after this.
The terminal S21 permits the operation of the device in IT-systems with
insulation monitoring, serves as a reference point for testing the control
voltage and is used to connect the E-stop loop when cross fault moni-
toring is selected.
Connecting the terminal S21 to the protective ground bridges the internal
short-circuit protection of Line A2(-). The short-circuit protection of line
A1(+) remains active.
Y39 - Y40 must be closed to have timed outputs. By opening the bridge
between Y39 and Y40 the time delay can be interrupted immediately. Wit-
hout bridge the contacts switch without delay.
The time setting has to be sealed by the user after test.
Signal designation
+ / L
- / N
Outputs
Positive driven NO contacts for
release circuit
NO contacts, delay
Positive guided indicator output

Technical Data

Input
Nominal voltage U
:
N
BH 5928:
BH 5928.92/900,
BI 5928.47/100:
Voltage range:
at 10% residual ripple:
at 48% residual ripple:
Nominal consumption:
Nominal frequency:
Min. Off-time:
Control voltage on S11:
Control current over
S12, S32:
Min. voltage on
S12, S32:
Short-circuit protection:
Overvoltage protection:
t
Output
Contacts
BH 5928.47, BI 5928.47/100:
BH 5928.91:
BH 5928.92
BH 5928.93:
The NC contacts 31-32 or 41-42 can only be used for monitoring.
Operate delay typ. at U
:
N
Manual start:
Automatic start:
Release delay typ. at U
:
N
Disconnecting the supply:
2-channel disconnecting
S12, S22, S31 and S32:
Fault detection time typ. at U
at 1-channel interruption
at S12, S22, and S31:
at S32:
Time delay tv
(release delayed):
Repeat accuracy:
Contact type:
Nominal output voltage:
Max switching current:
Switching of low loads:
(Contact 5 µ Au)
Thermal current I
:
th
in 1 contact path:
Switching capacity
to AC 15
NO contact:
NC contact:
to DC 13
NO contact:
NC contact:
BH 5928.47
NO contact 57/58:
to DC 13
NO contact:
NC contact:
Electrical life
to AC 15 at 2 A, AC 230 V:
Permissible operating
frequency:
Short circuit strength
max. fuse rating:
Mechanical life:
17
DC 24 V, AC/DC 24 V
DC 24 V
DC
AC/DC
0.9 ... 1.1 U
0.95 ... 1.1 U
N
0.8 ... 1.1 U
0.8
... 1.1 U
N
AC approx. 6.0 VA
DC approx. 3.5 W
50 / 60 Hz
1 s
DC 23 V at U
N
40 mA at U
each
N
DC 21 V when relay activated
Internal PTC
Internal VDR
3 NO, 1 NC contacts instantaneous and
1 NO contact release delayed
2 NO contacts instantaneous, and
2 NO contacts release delayed
2 NO, 1 NC contacts instantaneous and
3 NO contacts release delayed
3 NO contacts instantaneous and
3 NO contacts release delayed
40 ms
500 ms
40 ms
15 ms
:
N
15 ms
520 ms
Auxilary supply must be connected for
time delay
Time ranges:
0.1 ...
1 s
3.0 ...
0.3 ...
3 s
6.0 ...
0.5 ...
5 s
30 ... 300 s
1.0 ... 10 s
Other ranges or values on request
Fixed values: 1 s, 3 s, 5 s, 10 s, 300 s
± 1 % of setting value
forcibly guided
AC 250 V
DC: see limit curve for arc-free operation
DC: see limit curve for arc-free operation
≥ 100 mV
≥ 1 mA
max. 5 A
(see quadratic total current limit curve)
3 A / AC 230V
IEC/EN 60 947-5-1
1 A / AC 230 V
IEC/EN 60 947-5-1
1 A / DC 24 V
IEC/EN 60 947-5-1
1 A / DC 24 V
IEC/EN 60 947-5-1
2 A / DC 24 V
IEC/EN 60 947-5-1
5 A / 24 V at 0.1 Hz
5 A / 24 V at 0.1 Hz
10
5
switching cycles IEC/EN 60 947-5-1
max. 1200 switching cycles / h with manual
restart and short release delay time
6 A gL
IEC/EN 60 947-5-1
10 x 10
switching cycles
6
BH 5928, BI 5928 / 16.02.17 en / 831
N
N
30 s
60 s