Adjustments; Pilot Burner Adjustment; Venturi Adjustment - Napoleon CBI3600-N Instructions D'installation Et D'opération

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Test after installing the appliance into a vented non-combustible fi replace in the following manner:
1. Close all doors and windows in the room; start exhaust fans in the home; turn the appliance blower off.
2. Set controls to "high" and light the appliance.
3. Wait 5 minutes. Light a match and hold it to the spill tube opening.
4.
Venting action is satisfactory if smoke is drawn into the spill tube. Venting action is unsatisfactory if the fl ame
and smoke are not drawn into the tube.
5. If venting action is unsatisfactory, turn the appliance off, wait 10 minutes and try again. If the smoke or fl ame is
still not drawn into the spill tube, turn the appliance off and check for vent blockage or restriction. If necessary,
consult with a qualifi ed air quality specialist.

6.0 ADJUSTMENTS

6.1

PILOT BURNER ADJUSTMENT

1.
Remove the pilot adjustment cap.
2.
Adjust the pilot screw to provide properly sized fl ame.
3.
Replace the adjustment cap.
6.2

VENTURI ADJUSTMENT

This appliance has an air shutter that has been factory set open according
to the chart below:
Regardless of venturi orientation, closing the air shutter will cause a more
yellow flame, but can lead to carbonization. Opening the air shutter will
cause a more blue flame, but can cause flame lifting from the burner ports.
The flame may not appear yellow immediately; allow 15 to 30 minutes for
the final flame colour to be established.
AIR SHUTTER ADJUSTMENT MUST ONLY BE DONE BY A QUALIFIED
INSTALLER!
VENTURI ADJUSTMENT CHART
FUEL
NG
LP
PILOT SCREW
GI3600
1/16 (2mm)
3/8 (10mm)
THERMOPILE
PILOT BURNER
VENTURI
BURNER
ORIFICE
49.1
W415-1362 / A / 09.15.16
15
EN
ELECTRODE
AIR
SHUTTER
OPENING