Optional Wall Switch; Gas Installation - Napoleon CBI3600-N Instructions D'installation Et D'opération

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

3.3

OPTIONAL WALL SWITCH

DO NOT CONNECT THE WALL SWITCH OR GAS VALVE DIRECTLY TO 110 VOLT ELECTRICITY.
For ease of accessibility, an optional remote wall switch may be installed in a convenient location. Route a
2 strand, solid core millivolt wire from the valve to the wall switch. The recommended maximum lead length
depends on wire size:
WIRE SIZE
14 gauge
16 gauge
18 gauge
Disconnect the existing wires from terminals 1 and 3 (from the
ON/OFF switch) and replace with the leads from the wall switch.
3.4

GAS INSTALLATION

RISK OF FIRE, EXPLOSION OR ASPHYXIATION. ENSURE THERE ARE NO IGNITION SOURCES SUCH AS
SUPPORT GAS CONTROL WHEN ATTACHING GAS SUPPLY PIPE TO PREVENT DAMAGING GAS LINE.
ALWAYS LIGHT THE PILOT WHETHER FOR THE FIRST TIME OR IF THE GAS SUPPLY HAS RUN OUT
WITH THE GLASS DOOR OPENED OR REMOVED. PURGING OF THE GAS SUPPLY LINE SHOULD BE
PERFORMED BY A QUALIFIED SERVICE TECHNICIAN. ASSURE THAT A CONTINUOUS GAS FLOW IS AT
THE BURNER BEFORE CLOSING THE DOOR. ENSURE ADEQUATE VENTILATION. FOR GAS AND
ALL GAS CONNECTIONS MUST BE CONTAINED WITHIN THE APPLIANCE WHEN COMPLETE.
HIGH PRESSURE WILL DAMAGE VALVE. DISCONNECT GAS SUPPLY PIPING BEFORE TESTING GAS
Installation and servicing to be done by a qualifi ed installer.
Move the appliance into position and secure.
If equipped with a fl ex connector the appliance is designed to accept a 1/2" (13mm) gas supply.
Without the connector it is designed to accept a 3/8" (9.5mm) gas supply. The appliance is equipped
with a manual shut off valve to turn off the gas supply to the appliance.
Connect the gas supply in accordance to local codes. In the absence of local codes, install to the
current CAN/CSA-B149.1 Installation Code in Canada or to the current National Fuel Gas Code, ANSI
Z223.1 / NFPA 54 in the United States.
When fl exing any gas line, support the gas valve so that the lines are not bent or kinked.
The gas line fl ex-connector should be installed to provide suffi cient movement for shifting the burner
assembly on its side to aid with servicing components.
Check for gas leaks by brushing on a soap and water solution. Do not use open fl ame.
!
MAX. LENGTH
100 feet (30.5m)
60 feet (18.3m)
40 feet (12m)
!
SPARKS OR OPEN FLAMES.
ELECTRICAL LOCATIONS, SEE "DIMENSIONS" SECTION.
LINE AT TEST PRESSURES ABOVE 1/2 PSIG.
VALVE SETTINGS HAVE BEEN FACTORY SET, DO NOT CHANGE.
FLEXIBLE
CONNECTOR
ADAPTER
FITTING
WARNING
3
TP
1
WARNING
SHUT OFF VALVE
50.5
30.1A
BLACK
PIPE
W415-1362 / A / 09.15.16
9
EN

Publicité

Chapitres

Table des Matières
loading

Ce manuel est également adapté pour:

Cbi3600-pGi3600-nGi3600-p

Table des Matières