INSTALLER: LEAVE THIS MANUAL WITH THE APPLIANCE.
CONSUMER: RETAIN THIS MANUAL FOR FUTURE REFERENCE.
NEVER LEAVE CHILDREN OR OTHER AT RISK INDIVIDUALS ALONE WITH THE APPLIANCE.
Certified to Canadian and American National Standards: ANSI Z21.50 and CSA 2.22 for vented decorative gas appliances.
CERTIFIED FOR CANADA AND UNITED STATES USING ANSI/CSA METHODS.
SAFETY INFORMATION
WARNING
!
If the information in these instructions
are not followed exactly, a fi re or
explosion may result causing property
damage, personal injury or loss of life.
- Do not store or use gasoline or other fl ammable
vapors and liquids in the vicinity of this or any
other appliance.
- WHAT TO DO IF YOU SMELL GAS:
Do not try to light any appliance.
Do not touch any electrical switch; do not use
any phone in your building.
Immediately call your gas supplier from a
neighbour's phone. Follow the gas supplier's
instructions.
If you cannot reach your gas supplier, call the
fi re department.
- Installation and service must be performed by a
qualifi ed installer, service agency or the supplier.
This appliance may be installed in an aftermarket,
permanently located, manufactured home (USA
only) or mobile home, where not prohibited by
local codes.
This appliance is only for use with the type of gas
indicated on the rating plate. This appliance is
not convertible for use with other gases, unless a
certifi ed kit is used.
Phone 1 (866) 820-8686 • www.continentalfi replaces.com • ask@continentalfi re.on.ca
$10.00
INSTALLATION AND
OPERATING INSTRUCTIONS
Wolf Steel Ltd., 24 Napoleon Rd., Barrie, ON, L4M 0G8 Canada /
103 Miller Drive, Crittenden, Kentucky, USA, 41030
CB42NTR / CB42NTRE
NATURAL GAS MODEL
CB42PTR / CB42PTRE
PROPANE GAS MODEL
FOR INDOOR USE ONLY!
DANGER
!
DO NOT TOUCH GLASS UNTIL
NEVER ALLOW CHILDREN TO
A barrier designed to reduce the risk of burns from
the hot viewing glass is provided with this appliance
and shall be installed for the protection of children
and other at-risk individuals.
AVERTISSEMENT
!
LA VITRE CHAUDE CAUSERA
NE PAS TOUCHER LA VITRE
AVANT QU'ELLE AIT REFROIDI.
ENFANTS TOUCHER LA VITRE.
HOT GLASS WILL CAUSE
BURNS.
COOLED.
TOUCH GLASS.
DES BRÛLURES.
1.31C
W415-1541 / C / 11.23.17
NE JAMAIS LAISSER LES
EN
FR
PG
67

Publicité

loading

Sommaire des Matières pour Napoleon CONTINENTAL FOYERS CB42NTR

  • Page 1 AVERTISSEMENT LA VITRE CHAUDE CAUSERA Wolf Steel Ltd., 24 Napoleon Rd., Barrie, ON, L4M 0G8 Canada / DES BRÛLURES. 103 Miller Drive, Crittenden, Kentucky, USA, 41030 NE PAS TOUCHER LA VITRE Phone 1 (866) 820-8686 •...
  • Page 2 table of contents NOTE: The camera icon indicates video tutorials are available as additional reference, visit http://mynapoleon.napoleonproducts.com/download/index/44/1 installation overview framing introduction minimum framing dimensions dimensions minimum enclosure clearances general instructions non-combustible facing material general information alcove clearances rating plate information recessed installation venting minimum mantel clearances...
  • Page 3 1.0 installation overview See the section “MINIMUM ENCLOSURE CLEARANCES” for drywall (or other combus- tible material). See the section “MINIMUM MANTEL CLEARANCES”. See the section “VENTING” and “INSTALLATION”. See the section “FRAMING”. See the section “MINIMUM FRAMING DIMENSIONS”. Side Wall See the section “RATING PLATE INFORMATION”.
  • Page 4 2.0 introduction WARNING • THIS APPLIANCE IS HOT WHEN OPERATED AND CAN CAUSE SEVERE BURNS IF CONTACTED. • ANY CHANGES TO THIS APPLIANCE OR ITS CONTROLS CAN BE DANGEROUS AND ARE PROHIBITED. • Do not operate appliance before reading and understanding operating instructions. Failure to operate appliance according to operating instructions could cause fi...
  • Page 5 dimensions W415-1541 / C / 11.23.17...
  • Page 6 general instructions WARNING ALWAYS LIGHT THE PILOT WHETHER FOR THE FIRST TIME OR IF THE GAS SUPPLY HAS RUN OUT, WITH THE GLASS DOOR OPENED OR REMOVED. PROVIDE ADEQUATE CLEARANCE FOR SERVICING AND OPERATING THE APPLIANCE. PROVIDE ADEQUATE VENTILATION. NEVER OBSTRUCT THE FRONT OPENING OF THE APPLIANCE. OBJECTS PLACED IN FRONT OF THE APPLIANCE MUST BE KEPT A MINIMUM OF 48 INCHES (121.9cm) FROM THE FRONT FACE OF THE APPLIANCE.
  • Page 7 general information FOR YOUR SATISFACTION, THIS APPLIANCE HAS BEEN TEST-FIRED TO ASSURE ITS OPERATION AND QUALITY! RATES AND EFFICIENCIES Altitude (FT) 0-4,500 0-4,500 Max. Input (BTU/HR) 22,000 22,000 Min. Inlet Gas Supply Pressure 4.5" (11mb) Water Column 11" (27mb) Water Column Max.
  • Page 8 WOLF STEEL LTD. SERIAL NUMBER/NO. DE SERIE: B42TR 24 NAPOLEON ROAD, BARRIE, ON, L4M 0G8 CANADA W385-2069 / B MATERIAL: .010 VELVET MATTE LEXAN AND/OR .050 HI-TEMP POLYESTER MIN. LETTERING FOR "NOT FOR USE WITH SOLID FUEL. ", "UN COMBUSTIBLE SOLIDE NE DOIT PAS ÊTRE UTILISÉ AVEC CELUI. " TO BE 10 POINT ARIAL, BOLD FACE, INSTALLER: It is your responsibility to check off the appropriate box on the rating plate according to UPPER CASE AND 2 POINT LEADING SPACING OR EQUIVALENT.
  • Page 9 3.0 venting WARNING RISK OF FIRE, MAINTAIN SPECIFIED AIR SPACE CLEARANCES TO VENT PIPE AND APPLIANCE. IF VENTING IS INCLUDED WITH SPACERS THE VENT SYSTEM MUST BE SUPPORTED EVERY 3FT (0.9m) FOR BOTH VERTICAL AND HORIZONTAL RUNS. USE SUPPORTS OR EQUIVALENT NON-COMBUSTIBLE STRAPPING TO MAINTAIN THE REQUIRED CLEARANCE FROM COMBUSTIBLES.
  • Page 10 venting lengths and components Use only Wolf Steel, Simpson Dura-Vent, Selkirk Direct Temp, American Metal Amerivent or Metal-Fab venting components. Minimum and maximum vent lengths, for both horizontal and vertical installations, clearances from vent pipes to combustibles and air terminal locations as set out in this manual apply to all vent systems and must be adhered to.
  • Page 11 typical vent installation 16" (40.6cm) MINIMUM 40 ft (12m) maximum 3 ft (1m) minimum 24" (61cm) maximum 8" (203mm) minimum 42 5/8" (108.3cm) minimum plus rise* TOP VENT * See "VENTING" section W415-1541 / C / 11.23.17...
  • Page 12 16" (40.6cm) minimum 40 ft (12m) maximum 3 ft (1m) minimum 20" (50.8cm) maximum 24 1/8" (61.3cm) 24 1/8" minimum plus rise* (61.3cm) REAR VENT * See "VENTING" section W415-1541 / C / 11.23.17...
  • Page 13 special vent installations 3.3.1 periscope termination Use the periscope kit to locate the air termination above grade. The periscope must be installed so that when fi nal grading is completed, the bottom air slot is located a minimum 12” (30.5cm) above grade. The maximum allowable vent length is 10’...
  • Page 14 minimum air terminal location clearances COVERED BALCONY APPLICATIONS ††* = 3 feet ≤ 15 feet = 2 x ACTUAL (4.6m) (0.9m) INSTALLATIONS CANADA U.S.A. 12” (30.5cm) 12” (30.5cm) Clearance above grade, veranda porch, deck or balcony. 12” (30.5cm) 9” (229mm) Clearance to windows or doors that open.
  • Page 15 venting application flow chart TOP EXIT Horizontal Termination Vertical Termination Vertical rise is equal Vertical rise is equal Vertical rise is less Vertical rise is less to or greater than to or greater than than horizontal run than horizontal run the horizontal run the horizontal run Horizontal run +...
  • Page 16 elbow vent length values FEET INCHES MILLIMETERS 1° 0.03 12.7 15° 0.45 152.4 30° 11.0 279.4 45° 1.35 16.0 406.4 90°* 32.0 812.8 * The fi rst 90° offset has a zero value and is shown in the formula as - 90° 15.1A top exit vertical termination ) <...
  • Page 17 ) > (V Simple venting configuration See graph to determine the required vertical rise V for the required horizontal run H (only one 90° elbow) 150 (381) 147 (373) REQUIRED VERTICAL 100 (254) RISE IN INCHES (CENTIMETERS) V 57 (145) 50 (127) 8 (20.3) 20 (6.1)
  • Page 18 rear exit horizontal termination ) < (V Simple venting configuration See graph to determine the required vertical rise V for the required (only two 90° elbows) horizontal run H 40 (12.2) 38.3 (11.7) REQUIRED 30 (9.1) VERTICAL RISE IN 20 (6.1) FEET (METERS) V 10 (3.1)
  • Page 19 ) > (V Simple venting configuration See graph to determine the required vertical rise V for the (only two 90° elbows) required horizontal run H Simple venting configuration 150(3810) See graph to determine 150(3810) 147 (3733.8 147 (3733.8 (only one 90° elbow) REQUIRED VERTICAL RISE IN 100 (2540)
  • Page 20 3.10 top and rear exit vertical termination ) < (V See graph to determine the required vertical rise V for the Simple venting configurations. required horizontal run H 40 (12.2) 30 (9.1) REQUIRED VERTICAL RISE IN FEET 20 (6.1) (METERS)V 10 (3.1) 3 (0.9) (1.5)
  • Page 21 ) > (V See graph to determine the required vertical rise V for the Simple venting configurations. required horizontal run H 20 (6.1) 19 (5.8) REQUIRED VERTICAL 10 (3.1) RISE IN FEET 3 (0.9) (METERS)V (1.5) (3.1) (4.6) (6.1) (7.6) (9.1) HORIZONTAL VENT RUN PLUS OFFSET IN FEET (METERS)H The shaded area within the lines represents acceptable...
  • Page 22 3.11 rear exit WARNING FAILURE TO CREATE A SEAL TO THE FIREBOX WITH THE EXHAUST COLLAR ASSEMBLY WILL CAUSE THE APPLIANCE TO FUNCTION IMPROPERLY AND CAN CAUSE INJURY OR PROPERTY DAMAGE. Fig. 1 Remove the safety screen and glass front, refer to " SAFETY SCREEN / DOOR REMOVAL AND INSTALLATION"...
  • Page 23 3.13 top exit WARNING FLUE PIPE FAILURE TO INSTALL THE COVER PLATE AND GASKET WILL CAUSE THE APPLIANCE TO WITH GASKET FUNCTION IMPROPERLY AND CAN CAUSE INJURY OR PROPERTY DAMAGE. TO TOP VENT GASKET This appliance is factory shipped as a rear vent model equipped with a #44 burner orifice. This orifice INTAKE COLLAR size is suitable for rear vent installations with 0"...
  • Page 24 4.0 installation WARNING ENSURE TO UNPACK ALL LOOSE MATERIALS FROM INSIDE THE FIREBOX PRIOR TO HOOKING UP THE GAS AND ELECTRICAL SUPPLY. IF YOUR APPLIANCE IS SUPPLIED WITH A REMOTE, ENSURE THE REMOTE RECEIVER IS IN THE “OFF” POSITION PRIOR TO HOOKING UP THE GAS AND ELECTRICAL SUPPLY TO THE APPLIANCE. FOR SAFE AND PROPER OPERATION OF THE APPLIANCE, FOLLOW THE VENTING INSTRUCTIONS EXACTLY.
  • Page 25 4.1.2 horizontal installation WARNING THE FIRESTOP ASSEMBLY MUST BE INSTALLED WITH THE VENT SHIELD TO THE TOP. TERMINALS MUST NOT BE RECESSED INTO A WALL OR SIDING MORE THAN THE DEPTH OF THE RETURN FLANGE OF THE MOUNTING PLATE. 11 1/8" This application occurs when venting through 14 1/2"...
  • Page 26 using flexible vent components WARNING DO NOT ALLOW THE INNER FLEX PIPE TO BUNCH UP ON HORIZONTAL OR VERTICAL RUNS AND ELBOWS. KEEP IT PULLED TIGHT. SPACERS ARE ATTACHED TO THE INNER FLEX PIPE AT PREDETERMINED INTERVALS TO MAINTAIN AN EVEN AIR GAP TO THE OUTER FLEX PIPE.
  • Page 27 4.2.2 vertical air terminal installation WARNING MAINTAIN A MINIMUM 2” (51mm) SPACE BETWEEN THE AIR INLET BASE AND THE STORM COLLAR. NOTE : Fastening hardware provided with appropriate roof terminal and liner kits. Fasten the roof support to the roof using 6 screws. The roof support is optional. In this case the venting is to be adequately supported using either an alternate method suitable to the authority having jurisdiction or the optional roof support.
  • Page 28 4.2.3 appliance vent connection Install the inner exhaust fl ue collar to the appliance. Secure #8 X 1/2” with a minimum of 3 #8 screws. Seal the joint and screw SELF holes using Mill Pac sealant (W573-0007) (not supplied). DRILLING Install the outer fl...
  • Page 29 4.3.2 vertical air terminal installation Move the appliance into position. INNER PIPE Fasten the roof support to the roof using the screws provided. The roof support is optional. In this case the venting is to be adequately supported using either an alternate method suitable to the authority having jurisdiction or the optional roof support.
  • Page 30 4.3.3 restricting vertical vents WARNING TURN OFF GAS AND ELECTRICAL SUPPLY BEFORE SERVICING THE APPLIANCE. APPLIANCE MAY BE HOT, DO NOT SERVICE UNTIL APPLIANCE IS COOL. FOR SAFE AND PROPER OPERATION OF THE APPLIANCE, FOLLOW THE VENTING INSTRUCTION EXACTLY TO AVOID DANGER OF SUFFOCATION KEEP THE PACKAGING BAG AWAY FROM BABIES AND CHILDREN. DO NOT USE IN CRIBS, BED, CARRIAGES OR PLAY PENS.
  • Page 31 vertical through existing chimney WARNING RISK OF FIRE! CO-AXIAL TO CO-LINEAR VENTING CONFIGURATIONS MUST ONLY BE USED IN A NON-COMBUSTIBLE CHIMNEY OR ENCLOSURE. INSTALLATION IN A COMBUSTIBLE ENCLOSURE COULD RESULT IN A FIRE. This appliance is designed to be attached to a 3” (76.2mm) co-linear aluminum fl ex vent system running the full length of a masonry chimney.
  • Page 32 mobile home installation This appliance must be installed in accordance with the manufacturer’s instructions and the Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280, in the United States or the Mobile Home Standard, CAN/CSA Z240 MH Series, in Canada. This appliance is only for use with the type(s) of gas indicated on the rating plate.
  • Page 33 optional wall switch WARNING DO NOT CONNECT EITHER THE WALL SWITCH, THERMOSTAT OR GAS VALVE DIRECTLY TO 110 VOLT ELECTRICITY. For ease of accessibility, an optional remote wall switch or millivolt thermostat may be installed in a convenient location. Route a 2 strand, solid core millivolt wire from the valve to the wall switch or millivolt thermostat. The recommended maximum lead length depends on wire size: WIRE SIZE MAX.
  • Page 34 minimum framing dimensions 35" 88.9cm 18 9/16" 47.1cm W415-1541 / C / 11.23.17...
  • Page 35 Minimum clearance to combustible construction from appliance and vent surfaces: Combustible Framing: 0" to stand-offs 1" (25mm) to bottom and sides of the vent pipe* 3" (76mm) to top of the vent pipe* Combustible Finishing: 0" to rear 0" to front face top and sides Top Exit 50 1/2"...
  • Page 36 minimum enclosure clearances TOP VENT TOP EXIT ENCLOSURE The appliance requires a minimum enclosure height of 50 1/2" (1282mm). For temperature requirements, the enclosure space around and above the appliance must be left unobstructed. NOTE: The vent shield is telescopic and must be adjusted to shield the full depth of the combustible wall penetration.
  • Page 37 MINIMUM REAR VENT CLEARANCES For rear vent termination not exceeding 10" (254mm) of horizontal vent run. NOTE: The vent shield is telescopic and must be adjusted to shield the full depth of the combustible wall penetration. REAR EXIT ENCLOSURE The appliance requires a minimum non-combustible enclosure height of 41 5/8" (1057mm). For temperature requirements, the enclosure space around and above the appliance must be left unobstructed.
  • Page 38 MAXIMUM REAR VENT CLEARANCES (EXAMPLE 1) For rear vent termination exceeding 10" (254mm) NOTE: The vent shield is telescopic and must be adjusted to shield the full depth of the combustible wall penetration. REAR EXIT ENCLOSURE The appliance requires a minimum enclosure height of 41 5/8" (1057mm). For temperature requirements, the enclosure space around and above the appliance must be left unobstructed.
  • Page 39 MAXIMUM REAR VENT CLEARANCES (EXAMPLE 2) NOTE: The vent shield is telescopic and must be adjusted to shield the full depth of the combustible wall penetration. REAR EXIT ENCLOSURE The appliance requires a minimum enclosure height of 41 5/8" (1057mm). For temperature requirements, the enclosure space around and above the appliance must be left unobstructed.
  • Page 40 NON-COMBUSTIBLE FACING MATERIAL non-combustible facing material WARNING: Non-combustible facing material must not project more than 4” (102mm) from the face of the door (all three sides). If greater projections are desired, increase the clearance to the sides and top by 2” (51mm) for every additional 1” (25mm) of projection. If using an optional surround, the same rule applies, starting from the top of the surround.
  • Page 41 recessed installation WARNING INSTALLING A TELEVISION OR OTHER ELECTRONICS ABOVE THE APPLIANCE MAY CAUSE DISCOLOURATION, MELTING OR DAMAGE TO THE ELECTRONICS. USE CLEARANCES AS GUIDELINES AND REFER TO YOUR MANUFACTURER’S INSTRUCTIONS FOR FURTHER INFORMATION. MINIMUM CLEARANCES CHART 6" (152mm) MAX 41 5/8"...
  • Page 42 minimum mantel clearances WARNING RISK OF FIRE, MAINTAIN ALL SPECIFIED AIR SPACE CLEARANCES TO COMBUSTIBLES. FAILURE TO COMPLY WITH THESE INSTRUCTIONS MAY CAUSE A FIRE OR CAUSE THE APPLIANCE TO OVERHEAT. ENSURE ALL CLEARANCES (I.E. BACK, SIDE, TOP, VENT, MANTEL, FRONT, ETC.) ARE CLEARLY MAINTAINED.
  • Page 43 6.0 finishing WARNING RISK OF FIRE! NEVER OBSTRUCT THE FRONT OPENING OF THE APPLIANCE. IF FINISHING THE FRONT OF THE APPLIANCE, IT MUST BE FINISHED WITH ANY NON- COMBUSTIBLE MATERIAL SUCH AS BRICK, MARBLE, GRANITE, ETC. DO NOT STRIKE, SLAM OR SCRATCH GLASS. DO NOT OPERATE APPLIANCE WITH GLASS REMOVED, CRACKED, BROKEN OR SCRATCHED.
  • Page 44 Leave a hand on the glass door during entire door removal. The glass door is secured to the firebox with two spring latches along the top and two along the bottom. Pull the handles of the latches forward, then lift the latches out from the door frame to release the top of the door.
  • Page 45 log placement WARNING FAILURE TO POSITION THE LOGS IN ACCORDANCE WITH THESE DIAGRAMS OR FAILURE TO USE ONLY LOGS SPECIFICALLY APPROVED WITH THIS APPLIANCE MAY RESULT IN PROPERTY DAMAGE OR PERSONAL INJURY. LOGS MUST BE PLACED IN THEIR EXACT LOCATION IN THE APPLIANCE. DO NOT MODIFY THE PROPER LOG POSITIONS, SINCE APPLIANCE MAY NOT FUNCTION PROPERLY AND DELAYED IGNITION MAY OCCUR.
  • Page 46 glowing embers Tear the embers into pieces and place along the front row of ports covering all of the burner area in front of the small logs. Care should be taken to shred the embers into thin, small irregular pieces as only the exposed edges of the fibre hairs will glow.
  • Page 47 battery back-up installation WARNING ENSURE THE GAS AND ELECTRICAL POWER TO THE APPLIANCE IS TURNED OFF. APPLIANCE MAY BE HOT, DO NOT SERVICE UNTIL THE APPLIANCE HAS COOLED. NOTE: In the event of a power failure your appliance can be operated using the battery back-up supplied. Before beginning installation, disconnect the gas and electrical power supply from the appliance.
  • Page 48 optional (AUB) blower installation WARNING ENSURE THE UNIT IS COMPLETELY COOL BEFORE STARTING INSTALLATION TO AVOID DANGER OF SUFFOCATION KEEP THE PACKAGING BAG AWAY FROM BABIES AND CHILDREN. DO NOT USE IN CRIBS, BED, CARRIAGES OR PLAY PENS. THIS BAG IS NOT A TOY. KNOT BEFORE THROWING AWAY.
  • Page 49 7.0 wiring diagram WARNING DO NOT WIRE 110 VOLTS TO THE VALVE OR WALL SWITCH This appliance comes equipped with a battery back-up. If this back-up is used, install 4AA batteries (not supplied) into the holder and connect to the wire harness. ACS/IPI SWITCH (OPTIONAL)
  • Page 50 8.0 operation (electronic) WARNING IF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACTLY, A FIRE OR EXPLOSION MAY RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE. ALWAYS LIGHT THE PILOT WHETHER FOR THE FIRST TIME OR IF THE GAS SUPPLY HAS RUN OUT WITH THE GLASS DOOR OPENED OR REMOVED.
  • Page 51 9.0 operation (millivolt) WARNING IF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACTLY, A FIRE OR EXPLOSION MAY RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE. ALWAYS LIGHT THE PILOT WHETHER FOR THE FIRST TIME OR IF THE GAS SUPPLY HAS RUN OUT WITH THE GLASS DOOR OPENED OR REMOVED.
  • Page 52 10.0 adjustment 10.1 pilot burner adjustment Adjust the pilot screw to provide properly sized fl ame. Turn in a clockwise direction to reduce the gas fl ow. Check Pressure Readings: Inlet pressure can be checked by turning screw (A) counter- clockwise 2 or 3 turns and then placing pressure gauge tubing over the test point.
  • Page 53 10.3 flame characteristics It’s important to periodically perform a visual check of the pilot and burner fl ames. Compare them to the illustrations provided. If any fl ame 3/8” - 1/2” appears abnormal call a service person. (9.5mm - 12.7mm) FLAME MUST ENVELOP UPPER 3/8"...
  • Page 54 11.0 maintenance MAINTENANCE WARNING MAINTENANCE MAINTENANCE TURN OFF THE GAS AND ELECTRICAL POWER BEFORE SERVICING THE APPLIANCE. APPLIANCE MAY BE HOT, DO NOT SERVICE UNTIL APPLIANCE HAS COOLED. DO NOT USE ABRASIVE CLEANERS. DO NOT PAINT THE PILOT ASSEMBLY. This appliance and its venting system should be inspected before use and at least annually by a qualifi ed service person.
  • Page 55 11.1 annual maintenance WARNING THE FIREBOX BECOMES VERY HOT DURING OPERATION. LET THE APPLIANCE COOL COMPLETELY OR WEAR HEAT RESISTANT GLOVES BEFORE CONDUCTING SERVICE. NEVER VACUUM HOT EMBERS. DO NOT PAINT THE PILOT ASSEMBLY. This appliance will require maintenance which should be planned on an annual basis. Service should include cleaning, battery replacement, venting inspection and inspection of the burner, media and fi...
  • Page 56 11.2 door glass replacement WARNING DO NOT USE SUBSTITUTE MATERIALS. GLASS MAY BE HOT, DO NOT TOUCH GLASS UNTIL COOLED. CARE MUST BE TAKEN WHEN REMOVING AND DISPOSING OF ANY BROKEN DOOR GLASS OR DAMAGED COMPONENTS. BE SURE TO VACUUM UP ANY BROKEN GLASS FROM INSIDE THE APPLIANCE BEFORE OPERATION.
  • Page 57 W415-1541 / C / 11.23.17...
  • Page 58 W415-1541 / C / 11.23.17...
  • Page 59 W415-1541 / C / 11.23.17...
  • Page 60 W415-1541 / C / 11.23.17...
  • Page 61 14.0 troubleshooting (electronic) WARNING ALWAYS LIGHT THE PILOT WHETHER FOR THE FIRST TIME OR IF THE GAS SUPPLY HAS RUN OUT, WITH THE GLASS DOOR OPEN OR REMOVED. TURN OFF THE GAS AND ELECTRICAL POWER BEFORE SERVICING THE APPLIANCE. APPLIANCE MAY BE HOT, DO NOT SERVICE UNTIL APPLIANCE HAS COOLED. DO NOT USE ABRASIVE CLEANERS.
  • Page 62 SYMPTOM PROBLEM TEST SOLUTION Continues to spark Short or loose Verify all connections. Verify the connections from the and pilot lights, but connection in sensor rod. pilot assembly are tight; also verify these connections are main burner will not not grounding out to any metal. light.
  • Page 63 15.0 troubleshooting (millivolt) WARNING ALWAYS LIGHT THE PILOT WHETHER FOR THE FIRST TIME OR IF THE GAS SUPPLY HAS RUN OUT, WITH THE GLASS DOOR OPEN OR REMOVED. TURN OFF THE GAS AND ELECTRICAL POWER BEFORE SERVICING THE APPLIANCE. APPLIANCE MAY BE HOT, DO NOT SERVICE UNTIL APPLIANCE HAS COOLED. DO NOT USE ABRASIVE CLEANERS.
  • Page 64 SYMPTOM PROBLEM TEST SOLUTION Pilot will not light. No spark at pilot burner. Check if pilot can be lit by a match. Check that the wire is connected to the push button igniter. Check if the push button igniter needs tightening. PILOT BURNER Replace the wire if the wire insulation is broken or frayed.
  • Page 65 16.0 warranty CONTINENTAL® products are manufactured under the strict Standard of the world recognized ISO 9001 : 2015 Quality Management System. CONTINENTAL® products are designed with superior components and materials assembled by trained craftsmen who take great pride in their work. The burner and valve assembly are leak and test-fi red at a quality test station. The complete appliance is again thoroughly inspected by a qualifi...
  • Page 66 7200, Route Transcanadienne, Montréal, Québec H4T 1A3 24 Napoleon Road, Barrie, Ontario, Canada L4M 0G8 214 Bayview Drive, Barrie, Ontario, Canada L4N 4Y8 103 Miller Drive, Crittenden, Kentucky, USA 41030 Phone: 1-866-820-8686 continentalfireplaces.com...
  • Page 67 à risque. ÉCRAN DE PROTECTION Wolf Steel Ltd., 24 Napoleon Rd., Barrie, ON, L4M 0G8 Canada / 103 Miller Drive, Crittenden, Kentucky, USA, 41030 Téléphone 1 (866) 820-8686 • www.napoleonfoyers.com • ask@napoleon.on.ca W415-1541 / C / 11.23.17 1.31C...
  • Page 68 table des matières NOTE: L'icône du camera indique que les vidéos sont disponibles comme une référence supplémentaire, visitez http://mynapoleon.napoleonproducts.com/download/index/44/1 vue d'ensemble de l'installation ossature dimensions minimales de l'ossature introduction dégagements minimaux de l'enceinte 102 dimensions matériau de finition incombustible instructions générales installation en alcôve informations générales installation encadrée...
  • Page 69 1.0 vue d'ensemble de l'installation Voir la section « DÉGAGEMENTS MINIMAUX DE L’ENCEINTE » pour les cloisons sèches (ou autre matériau combustible). Voir la section « DÉGAGEMENTS MINIMAUX DE LA TABLETTE ». Voir les sections « ÉVACUATION » et « INSTALLATION ». Voir la section «...
  • Page 70 2.0 introduction AVERTISSEMENT • CET APPAREIL EST CHAUD LORSQU’IL FONCTIONNE ET PEUT CAUSER DE GRAVES BRÛLURES EN CAS DE CONTACT. • TOUTE MODIFICATION APPORTÉE À CET APPAREIL OU AUX CONTRÔLES PEUT ÊTRE DANGEREUX ET SONT INTERDIT. AVERTISSEMENT • Ne faites pas fonctionner l’appareil avant d’avoir lu et compris les instructions d’opération. Omettre d’utiliser l’appareil selon les instructions d’opération pourrait causer un incendie ou des blessures.
  • Page 71 B35 ILLUSTRATED 46mm 890mm dimensions 18 7/8" 480mm 7" 178mm 34 5/8" 4" [ 879mm ] SAFETY BARRIER 24 1/8" ÉCRAN DE PROTECTION 102mm 613mm 7 3/16" 11 5/16" [ 182mm ] 288mm 18 5/16" ENTRÉE INLET 42" 465mm 2 3/16" DU GAZ 1067mm 56mm...
  • Page 72 instructions générales AVERTISSEMENT ALLUMEZ TOUJOURS LA VEILLEUSE, QUE CE SOIT POUR LA PREMIÈRE FOIS OU LORSQUE L’APPROVISIONNEMENT EN GAZ EST ÉPUISÉ, AVEC LA PORTE VITRÉE OUVERTE OU RETIRÉE. PRÉVOYEZ UN ACCÈS SUFFISANT POUR ENTRETENIR ET OPÉRER L’APPAREIL. ASSUREZ-VOUS D'UNE QUANTITÉ SUFFISANTE D’AIR DE VENTILATION. N’OBSTRUEZ JAMAIS L’OUVERTURE DE L’APPAREIL.
  • Page 73 informations générales POUR VOTRE SATISFACTION, CET APPAREIL A ÉTÉ MIS À L'ESSAI POUR CONFIRMER SON FONCTIONNEMENT ET SA QUALITÉ! RENDEMENTS ET EFFICACITÉS CB42 Altitude (PI) 0-4,500 0-4,500 Débit max. (BTU/H) 22 000 22 000 Pression minimale d'alimentation en gaz 4.5" (11mb) w.c. 11"...
  • Page 74 WOLF STEEL LTD. SERIAL NUMBER/NO. DE SERIE: B42TR 24 NAPOLEON ROAD, BARRIE, ON, L4M 0G8 CANADA W385-2069 / B MATERIAL: .010 VELVET MATTE LEXAN AND/OR .050 HI-TEMP POLYESTER MIN. LETTERING FOR "NOT FOR USE WITH SOLID FUEL. ", "UN COMBUSTIBLE SOLIDE NE DOIT PAS ÊTRE UTILISÉ AVEC CELUI. " TO BE 10 POINT ARIAL, BOLD FACE, UPPER CASE AND 2 POINT LEADING SPACING OR EQUIVALENT.
  • Page 75 3.0 évacuation AVERTISSEMENT RISQUE D’INCENDIE. CONSERVEZ LES DÉGAGEMENTS NÉCESSAIRES AU CONDUIT D’ÉVENT ET À L’APPAREIL. SI LE SYSTÈME D’ÉVENT EST FOURNI AVEC DES ESPACEURS, LES COURSES HORIZONTALES ET VERTICALES DU SYSTÈME DOIVENT ÊTRE SUPPORTÉES À TOUS LES 3 PI (0,9m). UTILISEZ DES SUPPORTS OU DES ATTACHES INCOMBUSTIBLES ÉQUIVALENTS AFIN DE MAINTENIR LE DÉGAGEMENT AUX MATÉRIAUX COMBUSTIBLES.
  • Page 76 longueurs des conduits d’évacuation et composants Utilisez uniquement des composants d’évacuation Wolf Steel, Simpson Dura-Vent, Selkirk Direct Temp, American Metal Amerivent ou Metal-Fab. Les minimums et maximums des longueurs d’évent, pour les installations verticales et horizontales, et les emplacements des terminaisons pour les deux systèmes sont précisés dans ce manuel et doivent être respectés.
  • Page 77 installations typiques d'évents 16" (40,6cm) MINIMUM 40 FT (12M) MAXIMUM 24" (61cm) 3 FT (1M) MAXIMUM MINIMUM 8" (203mm) MINIMUM 42 5/8" (108,3cm) MINIMUM PLUS LA PENTE* ÉVACUATION SUR LE DESSUS * Voir la section « ÉVACUATION » W415-1541 / C / 11.23.17...
  • Page 78 16" (40,6cm) MINIMUM 40 FT (12M) MAXIMUM 3 FT (1M) MINIMUM 20" (50,8cm) 24 1/8" (61,3mm) plus la pente 24 1/8" (61,4cm) ÉVACUATION SUR L’ARRIÈRE * Voir la section « ÉVACUATION » W415-1541/ C / 11.23.17...
  • Page 79 installations particulières d'évents 3.3.1 ensemble périscopique Utilisez l’ensemble périscopique afi n de positionner la terminaison au-dessus du niveau du sol. L’ensemble périscopique doit être installé de façon à ce que la fente d’air du bas soit située à un minimum de 12 pouces (30,5cm) au-dessus du niveau du sol.
  • Page 80 emplacement et dégagements minimaux de la terminaison APPLICATIONS POUR BALCON COUVERT ††* INSTALLATION = 3 pieds ≤ 15 pieds = 2 x RÉELLE (0,9m) (4,6m) CANADA É.-U. 12” 12” (304,8mm) Dégagement au-dessus du sol, d’une véranda, d’une terrasse en bois ou d’un balcon. (304,8mm) 12”...
  • Page 81 charte d'application des évacuations ÉVACUATION SUR LE DESSUS Terminaison horizontale Terminaison verticale La course verticale La course verticale La course verticale est La course verticale est est plus petite que la est plus petite que la plus grande ou égale à plus grande ou égale à...
  • Page 82 légende Les symboles suivants sont utilisés dans le calcul et les exemples d’évacuation : > - plus grand que > - plus grand ou égal à < - plus petit que < - plus petit ou égal à - total de la longueur des courses horizontales (Hr) et des déviations (Ho) en pieds - longueur des courses horizontales combinées en pieds - facteur de la valeur d’une déviation : 0,03 (du total des degrés de déviation - 90°*) en pieds - longueur des courses verticales combinées en pieds...
  • Page 83 ) > (V Configuration d'évacuation simple Consultez le graphique pour déterminer la course verticale nécessaire V par rapport à la course horizontale requise H (un coude de 90° seulement) 150 (381) 147 (373) COURSE VERTICALE 100 (254) REQUISE EN POUCES (CENTIMÈTRES)V 57 (145) 50 (127)
  • Page 84 évacuation sur l'arriére terminaison horizontale ) < (V Configuration d'évacuation simple Consultez le graphique pour déterminer la course verticale nécessaire (deux coudes de 90° seulement) par rapport à la course horizontale requise H 40 (12,2) 38,3 (11,7) COURSE 30 (9,1) VERTICALE REQUISE EN PIEDS...
  • Page 85 ) > (V Configuration d'évacuation simple Consultez le graphique pour déterminer la course verticale (deux coudes de 90° seulement) nécessaire V par rapport à la course horizontale requise H 150(3810) 147 (3733,8) COURSE VERTICALE 100 (2540) REQUISE EN PIEDS (MÈTRES) V (1676,4) 50 (1270) 12 (304,8)
  • Page 86 3.10 évacuation sur l'arriére et au dessus terminaison verticale ) < (V Consultez le graphique pour déterminer la course verticale Configurations d'évacuation simples. nécessaire V par rapport à la course horizontale requise H 40 (12,2) 30 (9,1) COURSE VERTICALE 20 (6,1) REQUISE EN PIEDS (MÈTRES) V...
  • Page 87 ) > (V Configurations d'évacuation simples. Consultez le graphique pour déterminer la course verticale nécessaire V par rapport à la course horizontale requise H 20 (6,1) 19 (5,8) COURSE VERTICALE REQUISE EN 10 (3,1) PIEDS (MÈTRES) V 3 (0,9) (1,5) (3,1) (4,6) (6,1)
  • Page 88 3.11 évacuation à l'arrière AVERTISSEMENT IL EST ESSENTIEL QUE LE COUVERCLE D’ÉVACUATION SOIT INSTALLÉ, SI NON L’APPAREIL NE FONCTIONNERA PAS CORRECTEMENT ET POURRAIT CAUSER DES BLESSURES OU DES DOMMAGES MATÉRIELS. Enlevez l'écran de protection et vitre de la porte, référer de la Fig.
  • Page 89 3.13 évacuation sur le dessus AVERTISSEMENT IL EST ESSENTIEL QUE LE COUVERCLE D’ÉVACUATION SOIT INSTALLÉ, SI NON L’APPAREIL NE FLUE PIPE FONCTIONNERA PAS CORRECTEMENT ET POURRAIT CAUSER DES BLESSURES OU DES WITH GASKET DOMMAGES MATÉRIELS. JOINT D’ÉTANCHÉITÉ TO TOP VENT Cet appareil est fabriqué...
  • Page 90 4.0 installation AVERTISSEMENT AVANT D’EFFECTUER LES BRANCHEMENTS POUR L’ALIMENTATION EN GAZ ET ÉLECTRIQUE, ASSUREZ-VOUS DE RETIRER TOUTE COMPOSANTE NON FIXÉE À L’INTÉRIEUR DE LA CHAMBRE DE COMBUSTION. SI VOTRE APPAREIL COMPREND UN SYSTÈME DE TÉLÉCOMMANDE, ASSUREZ-VOUS QUE LE RÉCEPTEUR EST À LA POSITION « OFF » AVANT D’EFFECTUER LES BRANCHEMENTS POUR L’ALIMENTATION EN GAZ ET ÉLECTRIQUE.
  • Page 91 4.1.1 installation horizontale AVERTISSEMENT L’ESPACEUR COUPE-FEU DOIT ÊTRE INSTALLÉ AVEC L’ÉCRAN PROTECTEUR ORIENTÉ VERS LE HAUT. LA TERMINAISON NE DOIT PAS ÊTRE ENCHÂSSÉE DANS LE MUR OU LE REVÊTEMENT EXTÉRIEUR PLUS QUE L’ÉPAISSEUR DE LA BRIDE DE LA PLAQUE DE MONTAGE. Cette confi...
  • Page 92 utilisation de composants flexibles d’évacuation AVERTISSEMENT NE LAISSEZ PAS LA GAINE FLEXIBLE SE TASSER CONTRE LES COURSES HORIZONTALES OU VERTICALES ET LES COUDES. GARDEZ-LA TENDUE. DES ESPACEURS SONT FIXÉS À LA GAINE FLEXIBLE À INTERVALLES PRÉDÉTERMINÉS AFIN DE GARDER CALFEUTRAGE UN ESPACE VIDE AVEC LE CONDUIT EXTÉRIEUR.
  • Page 93 4.2.2 installation de la terminaison verticale AVERTISSEMENT CONSERVEZ UN ESPACE MINIMAL DE 2" (51mm) ENTRE LA BASE DE LA PRISE D’AIR ET LE COLLET DE SOLIN. NOTE : Matériel de fi xation fourni avec les ensembles de terminal pour toit et raccord appropriées. Fixez le support de toit au toit à...
  • Page 94 4.2.3 raccordement des évents à l'appareil Raccordez la collet d’évacuation à l’appareil. Fixez avec un minimum de trois vis #8. Scellez le joint et les têtes de vis AUTOPER- avec le scellant à haute température Mill-Pac W573-0007 CEUSES (non fourni). #8 X 1/2”...
  • Page 95 4.3.2 installation de la terminaison verticale Mettez l’appareil en place. CONDUIT Fixez le support de toit au toit à l’aide des vis fournies. Le support de INTÉRIEUR toit est optionnel. Dans ce cas, l’évent doit être supporté adéquatement, soit en utilisant une méthode alternative se conformant aux normes des autorités compétentes, soit en utilisant le support de toit optionnel.
  • Page 96 4.3.3 renstreignant des évents verticaux AVERTISSEMENT METTEZ HORS TENSION DE GAZ ET DE L'ALIMENTATION ÉLECTRIQUE AVANT D'INTERVENIR SUR L'APPAREIL. APPAREIL PEUT ÊTRE CHAUD, PAS DE SERVICE JUSQU'À CE QUE L'APPAREIL EST REFROIDI. AVERTISSEMENT POUR UNE UTILISATION SÛRE ET CORRECTE DE L'APPAREIL, SUIVEZ LES INSTRUCTIONS D'ÉVACUATION EXACTEMENT POUR ÉVITER LE RISQUE D'ASPHYXIE PAS LE SAC D'EMBALLAGE DE BÉBÉS ET LES ENFANTS.
  • Page 97 terminaison verticale à travers une cheminée existante AVERTISSEMENT RISQUE D'INCENDIE! LES CONFIGURATIONS D'ÉVACUATION COAXIALES À COLINÉAIRES NE DOIVENT ÊTRE UTILISÉES QUE DANS UNE CHEMINÉE OU UNE ENCEINTE DE NATURE INCOMBUSTIBLE. UNE INSTALLATION DANS UNE ENCEINTE COMBUSTIBLE PEUT CAUSER UN INCENDIE. Cet appareil est conçu pour être raccordé...
  • Page 98 INSTALLATION DANS UNE MAISON MOBILE Cet appareil doit être effectuée en respectant les directives du fabricant et le Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280, aux États-Unis, ou les normes actuelles pour les maisons mobiles, CAN/CSA Z240 SÉRIE MH, au Canada. Cet appareil ne doit être utilisé qu’avec le type de gaz indiqué sur la plaque d’homologation.
  • Page 99 interrupteur mural optionnel AVERTISSEMENT NE RACCORDEZ PAS L’INTERRUPTEUR MURAL, LE THERMOSTAT OU LA SOUPAPE DE GAZ À L’ALIMENTATION ÉLECTRIQUE DE 110 VOLTS. Pour faciliter l’accès, un interrupteur mural ou un thermostat millivolt optionnel peut être installé à un endroit pratique. Passez un fi l millivolt à deux brins (noyau solide) de la soupape à l’interrupteur mural ou au thermo- stat millivolt.
  • Page 100 18 9/16" 47.1cm dimensions minimales de l'ossature 35" 88,9cm 18 9/16" 47,1cm W415-1541/ C / 11.23.17...
  • Page 101 Dégagements minimaux de l'appareil aux matériaux combustibles : Ossature combustible : 0" aux espaceurs 1" (25mm) en dessous et sur les côtés du conduit d’évent* 3" (76mm) au-dessus du conduit d’évent* Finition combustible : 0" à l’arrière 0" des côtés et du dessus en façade Évacuation sur le dessus: 50 1/2"...
  • Page 102 dégagements minimaux de l'enceinte ÉVACUATION SUR LE DESSUS ENCEINTE AVEC ÉVACUATION SUR LE DESSUS L'enceinte de l'appareil doit avoir une hauteur minimale de 50 1/2" (1283mm). Afin de respecter les contraintes de température, l’espace à l’intérieur de l’enceinte, autour de l'appareil et au-dessus, doit demeurer sans obstruction. NOTE: L'écran protection est télescopique et doivent être ajusté...
  • Page 103 DÉGAGEMENTS MINIMAUX DE ÉVACUATION À L'ARRIÈRE Pour la ventilation arrière ne dépassement pas 10" (254mm) de section horizontale de ventilation. NOTE: L'écran protection est télescopique et doivent être ajusté à protection toute la profondeur de la pénétration de la paroi combustible. ENCEINTE AVEC ÉVACUATION À...
  • Page 104 DÉGAGEMENTS MAXIMAUX DE ÉVACUATION À L'ARRIÈRE (EXEMPLE 1) Pour la ventilation arrière dépassement de 10" (254mm) NOTE: L'écran protection est télescopique et doivent être ajusté à protection toute la profondeur de la pénétration de la paroi combustible. ENCEINTE AVEC ÉVACUATION À L'ARRIÈRE L'enceinte de l'appareil doit avoir une hauteur minimale de 41 5/8"...
  • Page 105 DÉGAGEMENTS MAXIMAUX DE ÉVACUATION À L'ARRIÈRE (EXEMPLE 2) NOTE: L'écran protection est télescopique et doivent être ajusté à protection toute la profondeur de la pénétration de la paroi combustible. ENCEINTE AVEC ÉVACUATION À L'ARRIÈRE L'enceinte de l'appareil doit avoir une hauteur minimale de 41 5/8" (1057mm). Afin de respecter les contraintes de température, l’espace à...
  • Page 106 matériau de finition incombustible AVERTISSEMENT: Les matériaux de finition incombustibles ne doivent pas dépasser de plus 4” (101,6mm) la façade de la porte (sur toutes côtés). Si des projections plus grandes sont requises, augmentez les dégagements des côtés et du dessus de 2"...
  • Page 107 5.5 installation encadrée AVERTISSEMENT L’INSTALLATION D’UNE TÉLÉVISION OU D’AUTRES APPAREILS ÉLECTRONIQUES DESSUS DE L’APPAREIL PEUT PROVOQUER LA DÉCOLORATION, FUSION OU DOMMAGE L’APPAREIL ÉLECTRONIQUE. UTILISER LES DÉGAGEMENTS À TITRE INDICATIF ET SE RÉFÉRER AUX AVERTISSEMENT INSTRUCTIONS DE VOTRE FABRICANT POUR PLUS D’INFORMATIONS. DÉGAGEMENTS MINIMUM 6"...
  • Page 108 dégagements minimaux de la tablette AVERTISSEMENT RISQUE D’INCENDIE. CONSERVEZ TOUS LES DÉGAGEMENTS AUX MATÉRIAUX COMBUSTIBLES SPÉCIFIÉS. NE PAS RESPECTER CES INSTRUCTIONS PEUT CAUSER UN INCENDIE OU UNE SURCHAUFFE. ASSUREZ-VOUS QUE TOUS LES DÉGAGEMENTS (ARRIÈRE, CÔTÉS, DESSUS, ÉVENTS, TABLETTE, FAÇADE, ETC.) SONT RESPECTÉS À LA LETTRE. LORSQUE VOUS UTILISEZ DE LA PEINTURE OU DU VERNIS COMME FINITION POUR VOTRE TABLETTE, ASSUREZ-VOUS QU’ILS SOIENT RÉSISTANTS À...
  • Page 109 6.0 finitions AVERTISSEMENT RISQUE D’INCENDIE! N’OBSTRUEZ JAMAIS L’OUVERTURE SUR LE DEVANT DE L’APPAREIL. SI LA FINITION DE LA FAÇADE DE L’APPAREIL EST FAIT, ELLE DOIT ÊTRE FAITE DE MATÉRIAU INCOMBUSTIBLE COMME DE LA BRIQUE, DU MARBRE, DU GRANITE, ETC. NE FRAPPEZ PAS, NE CLAQUEZ PAS ET N’ÉGRATIGNEZ PAS LA PORTE VITRÉE. NE FAITES PAS FONCTIONNER L’APPAREIL LORSQUE LA PORTE VITRÉE EST ENLEVÉE, FISSURÉE, BRISÉE OU ÉGRATIGNÉE.
  • Page 110 Laissez une main sur la porte vitrée pendant l'enlèvement de la porte. La porte vitrée est maintenue en place par deux loquets située en haut et deux loquets en bas de la porte. Tirez les poignées des loquets vers l’avant, puis retirez les loquets du cadre de porte afin de libérer le haut de la porte.
  • Page 111 disposition des bûches AVERTISSEMENT OMETTRE DE POSITIONNER LES BÛCHES CONFORMÉMENT AUX SCHÉMAS OU OMETTRE D’UTILISER UNIQUEMENT DES BÛCHES SPÉCIFIQUEMENT APPROUVÉES POUR CET APPAREIL PEUT CAUSER DES DOMMAGES MATÉRIELS OU DES BLESSURES CORPORELLES. LES BÛCHES DOIVENT ÊTRE PLACÉES CORRECTEMENT À L’INTÉRIEUR DE L’APPAREIL. NE CHANGEZ PAS LA POSITION DES BÛCHES CAR L’APPAREIL RISQUE DE NE PAS FONCTIONNER ADÉQUATEMENT ET UN RETARD D’ALLUMAGE RISQUE DE SE PRODUIRE.
  • Page 112 braises incandescentes Déchirez les braises incandescentes en morceaux et placez-les le long de la première rangée des orifices du brûleur en couvrant toute la surface à l’avant des petites bûches. Les braises devraient être déchirées très soigneusement en petits morceaux minces irréguliers, car seuls les côtés exposés des fibres deviendront incandescents. Les braises seront incandescentes seulement lorsqu'elles sont exposées à...
  • Page 113 installation du sauvegarde de pile AVERTISSEMENT ASSURER-VOUS QUE L'ALIMENTATION ÉLECTRIQUE ET LE GAZ À L'APPAREIL EST ÉTEINT. ASSUREZ-VOUS QUE L’APPAREIL EST COMPLÈTEMENT REFROIDI AVANT DE COMMENCER SERVICE. NOTE: En cas d’une panne de courrant votre appareil peut fonctionner utilisant le sauvegarde de pile AVERTISSEMENT fourni.
  • Page 114 installation de la soufflerie optionnelle (AUB) AVERTISSEMENT ASSUREZ-VOUS QUE L’APPAREIL EST COMPLÈTEMENT REFROIDI AVANT DE COMMENCER L’INSTALLATION . AFIN D’ÉVITER LES RISQUES DE SUFFOCATION, GARDEZ LE SAC D’EMBALLAGE LOIN DES BÉBÉS ET DES JEUNES ENFANTS. NE LE LAISSEZ PAS TRAÎNER DANS LES BERCEAUX, LES LITS, LES POUSSETTES OU LES AVERTISSEMENT PARCS DE JEU.
  • Page 115 schéma de câblage (électronique) AVERTISSEMENT NE RACCORDEZ PAS L’INTERRUPTEUR MURAL OU LA SOUPAPE DE GAZ À L’ALIMENTATION ÉLECTRIQUE (110 VOLTS) Cette appareil est fourni avec une sauvegarde de pile. Si la sauvegarde est utilisé, installez 4 piles « AA » (non-fourni) dans la boîtier de piles et connectez au harnais de fi...
  • Page 116 7.0 fonctionnement (électronique) AVERTISSEMENT SI CES INSTRUCTIONS NE SONT PAS SUIVIES À LA LETTRE, UN INCENDIE OU UNE EXPLOSION POURRAIENT S’ENSUIVRE, CAUSANT DES DOMMAGES MATÉRIELS,DES BLESSURES CORPORELLES OU DES PERTES DE VIE. ALLUMEZ TOUJOURS LA VEILLEUSE, QUE CE SOIT POUR LA PREMIÈRE FOIS OU LORSQUE L’APPROVISIONNEMENT EN GAZ EST ÉPUISÉ, AVEC LA PORTE VITRÉE OUVERTE OU RETIRÉE.
  • Page 117 8.0 fonctionnement (millivolt) AVERTISSEMENT SI CES INSTRUCTIONS NE SONT PAS SUIVIES À LA LETTRE, UN INCENDIE OU UNE EXPLOSION POUR- RAIENT S’ENSUIVRE, CAUSANT DES DOMMAGES MATÉRIELS, DES BLESSURES CORPORELLES OU DES PERTES DE VIE. ALLUMEZ TOUJOURS LA VEILLEUSE, QUE CE SOIT POUR LA PREMIÈRE FOIS OU LORSQUE L’APPROVISIONNEMENT EN GAZ EST ÉPUISÉ, AVEC LA PORTE VITRÉE OUVERTE OU RETIRÉE.
  • Page 118 PILOT ELECTRODE BURNER 9.0 réglages 3/8” - 1/2” (9.5mm - 12.7mm) réglage de la veilleuse FLAME SENSOR Ajustez la vis de la veilleuse pour obtenir une fl amme de taille normale. Tournez vers la droite pour réduire l’apport de gaz. VÉRIFIER LA PRESSION : FLAME MUST ENVELOP Pour vérifi...
  • Page 119 caractéristiques de la flamme Il est important d’effectuer périodiquement une inspection 3/8” - 1/2” visuelle de la fl amme de la veilleuse et du brûleur. (9,5mm - 12,7mm) Comparez-les à ces illustrations. Si des fl ammes paraissent anormales, contactez un technicien de service. LA FLAMME DOIT ENVELOPPER LA PARTIE SUPÉRIEURE...
  • Page 120 10.0 entretien AVERTISSEMENT COUPEZ L’ALIMENTATION EN GAZ ET L’ALIMENTATION ÉLECTRIQUE AVANT DE PROCÉDER À L’ENTRETIEN DE L’APPAREIL. L’APPAREIL PEUT ÊTRE CHAUD. ATTENDEZ QU’IL SOIT REFROIDI AVANT D’EN FAIRE L’ENTRETIEN. N’UTILISEZ PAS DE PRODUITS ABRASIFS. NE PEINTURE PAS L’ASSEMBLAGE DU VEILLEUSE. Assurez-vous que l’appareil fonctionne adéquatement une fois l’entretien terminé.
  • Page 121 10.1 entretien annuel AVERTISSEMENT LE CAISSON DEVIENT TRÈS CHAUD LORS DU FONCTIONNEMENT. LAISSEZ L’APPAREIL SE REFROIDIR COMPLÈTEMENT OU PORTEZ DES GANTS ANTICHALEUR AVANT D’EFFECTUER L’ENTRETIEN. AVERTISSEMENT NE JAMAIS ASPIRER DES BRAISES QUI SONT CHAUDES. NE PEINTUREZ PAS L’ASSEMBLAGE DE LA VEILLEUSE. Cet appareil nécessite un entretien qui devra être effectué...
  • Page 122 10.2 remplacement de la vitre de porte AVERTISSEMENT N’UTILISEZ PAS DE MATÉRIAUX DE SUBSTITUTION. LA VITRE PEUT ÊTRE CHAUDE, NE TOUCHEZ PAS LA VITRE JUSQU’À CE QU’ELLE AIT REFROIDI. UTILISEZ DE PRUDENCE LORSQUE VOUS ENLEVEZ ET JETEZ DES DÉBRIS DE VERRE WARNING OU DES COMPOSANTS ENDOMMAGÉS.
  • Page 123 W415-1541 / C / 11.23.17...
  • Page 124 W415-1541/ C / 11.23.17...
  • Page 125 W415-1541 / C / 11.23.17...
  • Page 126 W415-1541/ C / 11.23.17...
  • Page 127 13.0 guide de dépannage (électronique) MAINTENANCE AVERTISSEMENT MAINTENANCE MAINTENANCE ALLUMEZ TOUJOURS LA VEILLEUSE, QUE CE SOIT POUR LA PREMIÈRE FOIS OU LORSQUE L’APPROVISIONNEMENT EN GAZ EST ÉPUISÉ, AVEC LA PORTE VITRÉE OUVERTE OU RETIRÉE. COUPEZ L’ALIMENTATION EN GAZ ET L’ALIMENTATION ÉLECTRIQUE AVANT DE PROCÉDER À L’ENTRETIEN DE L’APPAREIL.
  • Page 128 SYMPTÔME PROBLÈME SOLUTIONS Continue de Court-circuit ou connexion Vérifi ez toutes les connexions. Vérifi ez si les connexions produire desserrée dans la tige de la de l’assemblage de la veilleuse sont serrées; vérifi ez des étincelles sonde. aussi si ces connexions ne causent pas de mise à la et la veilleuse terre au niveau du métal.
  • Page 129 14.0 guide de dépannage (millivolt) AVERTISSEMENT MAINTENANCE MAINTENANCE MAINTENANCE ALLUMEZ TOUJOURS LA VEILLEUSE, QUE CE SOIT POUR LA PREMIÈRE FOIS OU LORSQUE L’APPROVISIONNEMENT EN GAZ EST ÉPUISÉ, AVEC LA PORTE VITRÉE OUVERTE OU RETIRÉE. COUPEZ L’ALIMENTATION EN GAZ ET L’ALIMENTATION ÉLECTRIQUE AVANT DE PROCÉDER À L’ENTRETIEN DE L’APPAREIL.
  • Page 130 SYMPTÔME PROBLÉME SOLUTIONS La veilleuse ne Aucune étincelle au brûleur de Vérifi ez si la veilleuse peut être allumée avec une allumette. s’allume pas. la veilleuse. Vérifi ez si le fi l est raccordé au bouton-poussoir d’ignition. Vérifi ez si le bouton-poussoir d’ignition doit être resserré. VEILLEUSE Remplacez le fi...
  • Page 131 15.0 garantie Les produits CONTINENTAL® sont fabriqués conformément aux normes strictes du Système De Gestion de la Qualité mondialement reconnu ISO 9001 : 2015. Les produits CONTINENTAL® sont conçus avec des composants et des matériaux de qualité supérieure, assemblés par des artisans qualifi és qui sont fi ers de leur travail. Le brûleur et le montage de la soupape subissent un test de détection de fuite et d’allumage à...
  • Page 132 7200, Route Transcanadienne, Montréal, Québec H4T 1A3 24 Napoleon Road, Barrie, Ontario, Canada L4M 0G8 214 Bayview Drive, Barrie, Ontario, Canada L4N 4Y8 103 Miller Drive, Crittenden, Kentucky, USA 41030 Phone: 1-866-820-8686 continentalfireplaces.com...