12.
To install Wall Sleeve into the wall opening:
With drain holes facing outside, position the sleeve towards
IOM
IOM
the wall until the support brackets are set on wall edge.
SLEEVE MUST BE FASTENED TO THE STRUCTURAL
WALL AND NOT TO THE FINISHED WALL.
MASONRY WALLS MUST HAVE A LINTEL TO
SUPPORT THE WALL, AS PER NATIONAL AND
4.4.3 Sealing: Wall Sleeve and Construction Wall
13.
After wall construction has been completed make sure to
completely fi ll the space between the wall sleeve and the
wall with Low Expanding Insulation Foam (FIG. 13 and
FIG 14).
Wait 8 hours minimum for foam to cure.
a. Caulk and seal all seams and openings between
the wall sleeve and the fi nished exterior and interior
walls (FIG 14). Seal the spaces using non-hardening
caulking compound. All seals must be weather tight
to prevent entrance of air, moisture and water into the
building.
b. The wall opening across the top and bottom of the Wall
Sleeve could be fl ashed if required (FIG 8).
c. All unused holes need to be sealed.
d. Prepare the Condo Pack unit for installation. For unit
support guides refer to "Unit Support" section.
CARE MUST BE TAKEN NOT TO PLUG THE DRAIN
OPENINGS IN THE BASE PANEL.
W415-2288 / 08.29.2019
a. Leave ¼ " space in between the wall and
the wall sleeve for insulating with Low
Expanding Insulation Foam (FIG 13).
Ensure parallel position between Wall
Sleeve and wall opening. Wall Sleeve must
be square for the Condo Pack to slide into it.
b. Attach Wall Sleeve to the building:
• Secure the support brackets to the wall
using fi ve screw holes on each side.
• Secure side panels into the structural wall
using fasteners.
IMPORTANT
!
LOCAL BUILDING CODES.
IMPORTANT
!
13
Leave ¼ " space in between the wall and the wall sleeve
for insulating with Low Expanding Insulation Foam.
wall
stud
!
14
Caulk seal around
I N S I D E wall
!
1/4" GAP
in between the wall
and the wall sleeve
wall sleeve
1/4" GAP
I N S I D E
O U T S I D E
Sleeve and
H68.3.5
1/4" gap for low
expanding foam
low expanding
insulation foam
Caulk seal around
Sleeve and
O U T S I D E wall
Wall Sleeve
1/4" gap for low
expanding foam