PACKAGED UNIT PREPARATION

• THIS UNIT MUST BE INSTALLED IN ACCORDANCE WITH ALL APPLICABLE CODES.
• THIS UNIT IS APPROVED FOR THRU-THE-WALL INSTALLATION ONLY.
• THESE INSTALLATION AND MAINTENANCE INSTRUCTIONS SHOULD BE LEFT WITH THE UNIT
FOR FUTURE REFERENCE.
Prior to installing the unit in the wall opening:
1. Remove the brackets connecting the unit to the skid.
1. The unit must be installed a minimum of 8" above fi nished fl oor.
a. If unit is installed in a storage garage, all ignition sources (electric contactors
and motors included) must be positioned at a minimum of 18" (457mm) above
the fl oor, and it must be protected from physical damage by vehicles.
2. The entire unit must not be installed outside. This unit is designed for indoor
installation on an exterior wall having an opening for condenser airfl ow.
3. The grille side of the unit must extend 1/2" Min. - 1" Max. beyond the exterior wall to
allow moisture that may enter the outdoor section to drain.
4. DO NOT install this unit at an exterior wall location that will position the bottom of
the wall grille below the exterior grade level. Below grade installation will allow the
accumulation of rain or snow into the wall sleeve and unit base, and could result in
water penetration into the building interior.
5. The grille side must be:
a. Kept free of any obstructions that could reduce or alter the air fl ow pattern.
b. The unit must be installed at least 3' (0.92m) from electric meters, gas meters,
regulators, and relief equipment.
6. Masonry walls must have a lintel to support the wall, as per National and local
building codes.
7. The interior of the unit may be installed with clearances noted on the nameplate to
adjacent combustible surfaces.
8. The unit shall not be installed directly on carpeting, tile or other combustible
material, except wood fl ooring.
9. In order to be able to remove the unit, at least 40" (101,5 cm) of open area must be
left unobstructed in front of the front doors.
10. Caulk and seal all spaces around the top, sides and bottom of the exterior grille
area, making sure that THE OPENINGS FOR DRAINAGE IN THE BOTTOM EDGE ARE
NOT BLOCKED. Refer to "Unit Location and Clearances".
NOTE
IMPORTANT
!
!
H8.3.5 _pg1
13
IOM
W415-2288 / 08.29.2019