Additional refrigerant

• System refrigerant volume is based on linear feet of liquid line pipe and indoor equipment model/quantity.
• Refer to the outdoor unit installation manuals for information regarding refrigerant volume for system components.
• See table below for additional refrigerant volumes for each air handler.
AM072TNZDCH_IM_DVM V-AHU_AA_EN_.indd 17
Model
AM012TNZDCH/AA
AM018TNZDCH/AA
AM024TNZDCH/AA
AM030TNZDCH/AA
AM036TNZDCH/AA
AM048TNZDCH/AA
AM054TNZDCH/AA
AM060TNZDCH/AA
AM072TNZDCH/AA
Additional refrigerant per indoor unit (oz.)
11.6
17.6
17.6
29.3
31
41.6
44.8
59.6
59.6
English
17