Arrangement:
Unit is shipped from the factory arranged to be installed in an upflow or horizontal left (right to left air flow) position.
Horizontal left means when the unit is laid on its side and you are facing the unit, the supply air opening is to the left and
the return opening is to the right. These models are field convertible to a horizontal right (left to right) air flow position.
Upflow application
In an upflow installation the discharge outlet is at the top. Care should be taken to insure unit is level to permit proper
condensate drainage. Normal upflow installation will be in a closet or basement. If installed in a closet, it must have a
platform framed in. The platform must have an opening centered in the closet that measures at least 12 inches in height
from the floor. A filter frame and filter can be used that covers the opening and is sealed to prevent air by-passing the filter.
A filter grille can be used that is located as described in RETURN AIR REQUIREMENTS section. The minimum filter size is
shown in the table below.
Standard throw away air filter @ 300 ft/min or less
800 CFM = 20 x 20 x 1
1000 CFM = 20 x 25 x 1
1200 CFM = 20 x 30 x 1
1400 CFM = 25 x 30 x 1
1600 CFM = 25 x 30 x 1
1800 CFM = 30 x 30 x 1
2000 CFM = 30 x 40 x 1 or two 30 x 20 x 1
2400 CFM = 30 x 40 x 1 or two 30 x 20 x 1
Another option is to use the Filter Base Accessory Kit. This filter base is placed on the closet floor and secured with screws.
The unit is placed on top of the filter base and secured to the base with screws. Use seal strip, tape or calking to seal
between the unit and the base.
Connect the supply air outlet to a plenum to the top of the unit and secure it with screws. Use a Non-tape sealant such as
mastic or an aerosol sealant to seal duct leakage. If installed in a basement, run supply and return duct work in accordance
with local codes. Use a Non-tape sealant such as mastic or an aerosol sealant to seal duct leakage.
AM072TNZDCH_IM_DVM V-AHU_AA_EN_.indd 11
Airflow
Horizontal left arrangement
Pleated Air Filter @ 500 ft/min or less
800 CFM = 16 x 16 x 1
1000 CFM = 18 x 20 x 1
1200 CFM = 20 x 20 x 1
1400 CFM = 20 x 20 x 1
1600 CFM = 20 x 25 x 1
1800 CFM = 20 x 30 x 1 or two 20 x 15 x 1
2000 CFM = 20 x 30 x 1 or two 20 x 15 x 1
2400 CFM = 25 x 30 x 1 or two 14 x 30 x 1
Airflow
English
11