APPENDIX
6.10. Appendix 10
Cable specification
1. Single phase unit
MCA
Phase line
No more
than 13A 2
1.3mm
13~18A 2
2.1mm
18~25A 2
3.3mm
25~30A 2
5.3mm
30~40A 2
8.4mm
40~55A 2
13 3mm
55~70A 2
21.2mm
MOP
MCB
No more
than 13A
20A 30mA less than 0.1 sec
13~25A
40A 30mA less than 0.1 sec
25~30A
40A 30mA less than 0.1 sec
30~40A
63A 30mA less than 0.1 sec
40~55A
80A 30mA less than 0.1 sec
55~70A
100A 30mA less than 0.1 sec
2. Three phase unit
Nameplate
maximum
Phase line AWG Neutral line Earth line
current
No more
than 13A
3 1.3mm
13~18A
3 2.1mm
18~25A
3 3.3mm
25~30A
3 5.3mm
30~40A
3 8.4mm
40~55A
3 13.3mm
55~70A
3 21.2mm
When the unit will be installed at outdoor, please use the cable which can against UV.
AWG
Earth line
2
16
1.3mm
2
14
2.1mm
2
12
3.3mm
2
10
5.3mm
2
8
8.4mm
2
6
13.3mm
2
4
21.2mm
Creepage protector
2
2
16
1.3mm
2
2
14
3.3mm
2
2
12
3.3mm
2
3.3mm
2
10
2
3.3mm
2
8
2
3.3mm
2
6
2
3.3mm
2
4
Signal line
2
2
2
2
n
0.5mm
2
2
2
2
Signal line
2
1.3mm
2
2.1mm
2
3.3mm
n
2
5.3mm
2
8.4mm
2
13.3mm
2
21.2mm
27
2
0.5mm