eassignment of conductors.
Given that we must adapt to the available wiring, in some installations we may have to reassign
some independent wires in order to use to reinforce the positive. This reassignment will be done in
the section between the door panel and the first distributor.
As a general rule, when the cross section of the positive wire is less than 0.5mm and a minimum of 5
independent wires dedicated to negative are available, then for each 3 independent wires we will
use 1 to reinforce the positive.
Independent wires used
for ground (5 minimum)
Independent wires used
to reinforce positive
If the riser wiring shows clear signs of deterioration or does not comply with the minimum
requirements (see page 91), then the installation riser must be replaced. For this, Golmar
recommends using the
condition then their replacement will not be necessary.
If you have doubts about how to allocate the available wires, please contact our technical-
commercial department.
cable. If the branch connections to the apartments are in good
RAP-8415
INSTALLATION