Stand-alone operation
Step 1: Setting ds2 and ds1 for stand-alone operation
DS-8 AC input
Set as desired
DS-7 AC input
Set as desired
DS-6 AC input
Set as desired
DS-5 AES
Set as desired
DS-4 Charging current Set as desired
DS-3 Charging current Set as desired
DS-2 Stand-alone operation
DS-1 Stand-alone operation
Examples of DIP switch settings for stand-alone mode are given below.
Example 1 shows the factory setting (since factory settings are entered by computer, all DIP switches of a new product are set to 'off'
and do not reflect the actual settings in the microprocessor.).
Four examples of stand-alone settings:
DS-8 AC input
on
DS-7 AC input
on
DS-6 AC input
on
DS-5 AES
off
DS-4 Ch. current
on
DS-3 Ch. current
off
DS-2 St.-alone mode
off
DS-1 St.-alone mode
off
Step1, stand-alone
Step1, stand-alone
Example 1 (factory setting):
Example 2:
8, 7, 6 AC-in: 50A*
8, 7, 6 AC-in: 50A*
5 AES: off
5 AES: off
4, 3 Charging current: 75%
4, 3 Charge: 100%
2, 1 Stand-alone mode
2, 1 Stand-alone
*Maximum is limited to 16A in case of models with 16A transfer switch
To store the settings after the required values have been set: press the 'Up' button for 2 seconds (upper button to the right of the DIP
switches, see appendix A, position J). The overload and low-battery LED's will flash to indicate acceptance of the settings.
We recommend making a note of the settings, and filing this information in a safe place.
The DIP switches can now be used to apply the remaining settings (step 2).
off
off
DS-8
on
DS-8
DS-7
on
DS-7
on
DS-6
on
DS-6
on
DS-5
off
DS-5
DS-4
on
DS-4
on
DS-3
on
DS-3
on
DS-2
off
DS-2
DS-1
off
DS-1
Step1, stand-alone
Example 3:
8, 7, 6 AC-in: 16A
5 AES: off
4, 3 Charge: 100%
2, 1 Stand-alone
off
DS-8
on
DS-7
on
DS-6
off
off
DS-5
on
DS-4
off
DS-3
on
off
DS-2
off
off
DS-1
off
Step1, stand-alone
Example 4:
8, 7, 6 AC-in: 30A*
5 AES: on
4, 3 Charge: 50%
2, 1 Stand-alone
17