3- Having reached the closed position, after 2 seconds the motors automatically will start the opening
manoeuvre. Wait for the manoeuvre to be completed (when the motors have stopped).
4- Now the gate is completely opened.
Let a T time elapse (fig.14 whatever you want); after which give a pulse that will close the sliding gate/boom
gate.
T becomes the T.C.A. (=AUTOMATIC RECLOSING TIME).
During all these phases the flascing light turns on.
5- Now work time and pause have been memorized.
Place the Dip-switch 4B back onto the MEMORIZING
EXCLUDED position = OFF position (fig. 15) and check that the flashing light turns off.
6- When the gate is being used normally it will close touching, while when it opens it will never reach the
theorical stop point.
PEDESTRIAN OPENING MEMORISATION FOR ONE MOTOR
1- Bring Dip 4B into the MEMORISATION ENABLE position; the blinking light will turn on.
2- Press the PEDESTRIAN push button; the wing gate will start opening or the sliding gate connected to the M1
motor.
3- Stop the gate by pressing the PEDESTRIAN push button in the point wanted.
4- Either press the PEDESTRIAN push button again or wait for the pause time to elapse for the gate to close.
5- Take Dip 4B back into the MEMORISATION EXCLUDED position and make sure the blinking light is off.
CONTROL CARD' RESET
If you wish to vary some or all the previously memorised settings proceed as follows:
1- power the control card;
2 - touch the two JP1 jump pins for at least 1 second with the tip of a screwdriver;
3 - the previously memorised settings have now been cancelled.
During this operation the position of dip 4B is irrelevant.
pag.20