Configuration and Operation
continued

Remote Monitoring and Control

Models PDUMH30ATNET, PDUMH30HVATNET and PDUMH32HVATNET provide remote
monitoring, outlet control and more via Web browser, telnet and SNMP-based
Network Management Systems. For more information about configuration and
operation of the PDU via the PowerAlert Web browser interface, refer to the
SNMPWEBCARD Installation Manual, downloadable at tripplite.com/support.
Load "Ramping" on Startup: All models arrive from the factory programmed so that,
when first powered up, their outlets turn on in sequential order at intervals of
approximately 250 ms. This prevents circuit overloads by staggering the startup of
multiple devices. Models PDUMH30ATNET, PDUMH30HVATNET and
PDUMH32HVATNET support user-programmable startup of outlets, in any order or
time interval. This ensures that network items are turned on in the proper sequence,
with the appropriate delay, so that network items are reliably discovered on startup.
Programmable Load "Shedding" During a Power Failure: In the event that the
primary power source fails and the PDU is relying on the secondary power source,
load shedding allows you to program the shutoff of specific outlets at timed intervals.
This enables you to turn off less critical loads (monitors, for example) to maximize the
UPS runtime for the most critical items.