Restore Factory Defaults; Static Pressure Function; Maintenance And Care; Outdoor Heat Exchanger - Gree GMV-80WL A-T Manuel De L'utilisateur

Système drv multiple de l'onduleur dc
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Press SW7 to confirm. When system enters this function, main board of outdoor unit will
display as below:
LED1
Function code
n3
Then unit will be in compulsory defrosting mode. Once unit is under compulsory defrosting,
this mode can only be stopped when requirements for exit are met.

8.4 Restore Factory Defaults

i.If you want to restore factory defaults, hold SW8 button on the main board of ODU for
more than 10s, then all LEDs will blink for 3s. Main board will cancel all setting, including the IP
addresses and project codes of IDU and ODU. The mark for finished debugging is "0".
ii.If you want to restore factory defaults and don't need project debugging, then hold SW3
and SW8 on the main board of ODU for more than 10s, then all LEDs will blink for 5s. All
settings are cleared out, including the IP addresses and project codes of IDU and ODU. The
mark for finished debugging remains the same.
iii.When you only want to restore the default functions, hold SW5 and SW8 button for more
than 10s, then all LED will blink for 7s. All function settings are cleared out, but IDU and ODU's
project codes and the mark for finished debugging remain the same.

8.5 Static Pressure Function

If ODU's installation area is not convenient for releasing air and users do not have strict
requirements for ODU noise, this function can be set to satisfy the heat exchange of ODU.
Before power on, set codes of SA6 of main board. The relevant static pressure is:
DIP1
0
1
Note: code of number side is "1"; default code of SA6 is "00".

9 Maintenance and Care

Regular check, maintenance and care can extend unit's service life. Please have
specialized person in charge of the management of air conditioners.

9.1 Outdoor Heat Exchanger

Outdoor heat exchanger shall be cleaned regularly, which is at least once every two
months. You can use a dust catcher with nylon brush to clean away the dust on the heat
exchanger. If compressed air source is available, it also can be used to clean the heat
exchanger. Do not clean it with water.
Copyright 2018. This translation is property of GREE PRODUCTS SL. All rights reserved. Total or partial reproduction without its express authorization is prohibited.
Display
Current progress/mode
On
Code setting SA6
DIP2
0
0
DC Inverter Multi VRF System User Manual
LED2
Display
00
On
40
LED3
Current status
Display
00
On
Static pressure
(Pa)
0
20

Publicité

Chapitres

Table des Matières
loading

Table des Matières