Technical Data
Supply circuit (via S-BUS)
Operating voltage U
, DC
B
Residual ripple Uss
Rated power
Input circuit (I1 – I8)
Input voltage U
(HIGH)
e
U
(LOW)
e
Input current I
(HIGH)
e
I
(LOW)
e
ON period t
E
OFF period t
A
Break time of U
(HIGH)
E
Synchronous time t
S
Output circuit (X1 – X8)
Output voltage
Output current per output
Test pulse width t
TI
Test pulse duration t
TD
Test pulse period T
PI
Operate time t
*
AN
Load capacitance C
L
Line length (simple,  1,5 mm
Short-circuit behaviour
General data
Isolation
Power circuitry – input circuit
Power circuitry – output circuit
Input circuit - output circuit
Weight

Climatic conditions

Ambient operating temperature T
Storage temperature
Relative humidity
Climatic conditions
Air pressure in operation
Mechanical strength
Vibration acc. to

Electrical safety

Protection class housing / terminals acc. to EN 60529
Finger-proof
Clearance/creepage distance
EMC
Overvoltage category
Contamination level
Terminals and connection
Single-core or finely stranded
Stripping length
Finely stranded with wire-end ferrule to DIN 46228
Max. tightening torque
* t
= Time between changing input signal on the input modules and switch off outputs Q1 ... Q4 of the assigned base module.
AN
10
Function 1, 2, 3, 4, 5, 6, 7, 8
Function 1, 2, 3, 4, 5, 6, 7, 8
Function 1
Function 6, 7
Function 2 (except safety mat), 3, 4, 5, 8
Function 2 (safety mat)
)
2
B
Min.
DC 19.2 V
--
--
Min.
13,0 V
-5,0 V
2,4 mA
-2,5 mA
70 ms
--
--
Min.
18.0 V
--
--
--
--
--
--
--
--
--
--
no
no
no
0.13 kg
-25C to +55C
-25C to +70C
10% to 95%, no condensation
EN 61131-2
860 hPa to 1060 hPa
EN 60068-2-xx (more data see manual)
IP 40 / IP 20
EN 50247
EN 61131-2
EN 61000-4-xx (more data see manual)
III
2 inside, 3 outside
screw-type terminals
1 x 0.2 - 2.5 mm² / 2 x 0.2 - 0.75 mm²
1 x 0.25 - 2.5 mm² / 2 x 0.25 - 0.5 mm²
0.5 to 0.6 Nm
Typ.
--
--
Typ.
--
--
3,0 mA
--
--
> operate time t
AN
--
--
Typ.
--
--
12 ms
20 ms
40 ms
--
--
--
--
--
--
Absolutely short-circuit-proof
spring-type terminals
2 x 0.2 - 1.5 mm²
max. 8 mm
2 x 0.25 - 1.5 mm² (trapezoid crimping)
---
Max.
DC 30 V
3.0 V
1.2 W
Max.
30 V
5,0 V
3,8 mA
2,1 mA
--
1.0 ms
1500 ms
Max.
--
150 mA
--
--
--
33 ms
16 ms
24 ms
42 ms
1000 nF