V. Wiring
The heat pump should only be wired in by a qualified professional in accordance with the rules of the art.
The power supply should be compatible with the model selected :
Supply voltage
(Volts/phases/Hz)
Electric current
requirement (A)
Cable cross section
(mm2)
Electrical
Not adjustable
protection
(A)
Adjustable
V.1 - Control panel side:
The line feeding the heat pump must be configured and fitted with one or more devices providing for:
- proper earthing of the machine
- protection of people by means of a 30 mA residual current device (interrupter or circuit breaker) dedicated to the
pool control panel or the heat pump line (unless the house is already fitted with one)
- Protection of the machine against "overloads" and short-circuits by means of a thermo-magnetic circuit-breaker
To avoid the untimely tripping of the circuit breakers on starting up the machine, use D curve circuit breakers.
V.2 - Connections on the heat pump side:
The machine is wired through the black connection box beside the information plate.
•
To remove the lid of the connection box, first unscrew the 4 plastic screws.
•
Push the power cable up through the cable gland situated at the bottom of the connection box.
•
Strip the first 1 cm of each wire and connect these to the domino connector, taking care to join the phase, live,
neutral, earth correctly (N.B. : on some single phase machines, the neutral wire is grey).
•
Tighten the cable gland nut to immobilise the cable and ensure that the seal around the cable is leaktight
•
Put back the lid back on the box and screw it into position.
HC-HH 62 M
HC-HH 72 M
230/1/50
230/1/50
7 to 8.5
10.5 to 12.5
2.5
4
12
16
Set the protection to be triggered at the upper electric current requirement + 2 A
Single phase
Black wire = phase
Blue wire = neutral
Yellow/green = earth
HC-HH 92 M
HC-HH 102 M
HC-HH 102 T
230/1/50
230/1/50
400/3/50
14 to 15
14.5 to 16.5
8.0 to 10.0
4
4
2.5
20
20
12
2009/01 - Indice de révision : C - Code : 0033385
36/48
HC-HH 122 M
HC-HH 152 M
HC-HH 122 T
HC-HH 152 T
230/1/50
230/1/50
400/3/50
400/3/50
16.5 to 18.5
8.5 to 10.5
8.5 to 10.5
4
6
2.5
4
20
16
HC-HH 172 T
230/3/50
9.0 to 10.5
4
20