Application Examples
L1
N
off
emergency-
stop
A1(+)
S33
A2(-)
Two-pole emergency stop circuit with emergency stop control device in
supply circuit with automatic ON-function.
Application for long emergency stop loops where the control voltage drops
below the minimum voltage of 21 V.
Attention:
Single faults (e.g. line faults at the emergency stop control device) are not
detected with this external circuit configuration.
Suited up to SIL2, Performance Level d, Cat. 3
L1
N
emergency-
stop
A1(+)
S33
A2(-)
Single-channel emergency stop circuit. This circuit does not have any
redundancy in the emergency stop control circuit
Suited up to SIL2, Performance Level d, Cat. 3
L1
A1(+)
S34
S33
S33 S33
A2(-)
Y1
N
activated NO contact
(contact position: closed)
Two-channel monitoring of a safety gate.
Suited up to SIL3, Performance Level e, Cat. 4
S12
S12
S22
S21
S23
BD5987.02/301
X5
X6
S12
S12
S22
S21
S23
BD5987.02/301
X5
X6
safety gate
closed
S1
on
S2
PE(-)
Y2
S12 S12
S22
13
BD5987
14
M6748_b
L1
13
23
A1(+)
S34
14
24
A2(-)
Y1
M6745_b
N
Contact reinforcement by external contactors, 2-channel.
The output contacts can be reinforced by external contactors with forcibly
guided contacts for switching currents > 10 A. Functioning of the external
contactors is monitored by looping the NC contacts into the closing circuit
(terminals Y2 - S12).
Suited up to SIL3, Performance Level e, Cat. 4
L1
A1(+)
13
23
A2(-)
14
24
M11385
N
Two-channel emergency stop circuit with cross fault detection.
Activation via On pushbutton. ---- Jumper X5 -X6:
Jumper X5 - X6 must be fitted for the automatic On function.
The On pushbutton is not required.
Suited up to SIL3, Performance Level e, Cat. 4
L1
23
A1(+)
24
A2(-)
N
Two-channel emergency-stop circuit without cross fault detection.
Activation via On pushbutton. ---- Jumper X5 - X6:
Jumper X5 - X6 must be fitted for the automatic On function.
The On pushbutton is not required.
Suited up to SIL3, Performance Level e, Cat. 4
19
K4
on
K5
S33
S33 S33
PE(-)
Y2
S12 S12
BD5987
emergency-
stop
S21
PE
S12
S22
S23
BD5987.02/001
S12
S33
X5
X6
on
emergency-
stop
S21
S12
PE
S22
S23
BD5987.02/001
S12
S33
X5
X6
on
emergency-
stop
S22
13
23
14
24
K4
K5
M6746_b
S33
13
23
S34
14
24
M6749_a
S33
13
23
S34
14
24
M6750_b
BD 5987 / 22.01.19 en / 088A