6. Drainage piping work
30
30
30
11
Fig. 6-2
7. Electrical work
S1
A Indoor unit
B Outdoor unit
C Wired remote controller
D Wired main switch/fuse
For Power supply
E Grounding
For Power
supply
Fig. 7-1
A Electric component cover
B Electric component box
C Entry for Indoor-Outdoor connecting cable
D Entry for wired remote controller cable
E Cable clamp
Fig. 7-2
Fig. 7-3
,
S1
S2
S3
1
2
S2
S3
F Indoor/Outdoor unit connecting terminal
G Wired remote controller terminal
(For SLZ-KA·VAQ3)
H Indoor controller
I Earth cable
1. Connect the drain socket (supplied with the unit) to the drain port. (Fig. 6-2)
(mm)
(Affix the tube using PVC adhesive then secure it with a band.)
2. Install a locally purchased drain pipe (PVC pipe, O.D. ø32).
(Affix the pipe using PVC adhesive then secure it with a band.)
3. Insulate the tube and pipe. (PVC pipe, O.D. ø32 and socket)
4. Check that drain flows smoothly.
5. Insulate the drain port with insulating material, then secure the material with a
band. (Both insulating material and band are supplied with the unit.)
A Main unit
B Insulating material
C Band (large)
D Drain port (transparent)
E Insertion margin
F Matching
7.1. Precautions (Fig. 7-1)
Electrical specification
Power supply
(1 phase ~/N, 230V,
50Hz)
• The compressor will not operate unless the power supply phase connection is cor-
rect.
• Grounding protection with a no-fuse breaker (earth leakage breaker [ELB]) is usually
installed for D.
• The connection wiring between the outdoor and indoor units can be extended up
to a maximum of 50 meters, and the total extension including the crossover wiring
between rooms is a maximum of 80 m.
A switch with at least 3.5 mm contact separation in each pole shall be provided by
the air conditioner installation.
* Label each breaker according to purpose (heater, unit etc.).
7.2. Indoor unit (Fig. 7-2) (Fig. 7-3)
Work procedure
1. R emove 2 screws to detach the electric component cover.
2. R oute each cable through the wiring intake into the electric component box. (Procure
power supply cable and indoor/outdoor connecting cable locally.)
3. S ecurely connect the power supply cable and the indoor/outdoor connecting cable
to the terminal blocks.
4. S ecure the cables with clamps outside the electric component box.
5. A ttach the electric component cover as it was.
• Fix power supply cable and indoor/outdoor connecting cable to electric component
box by using buffer bushing for tensile force. (PG connection or the like.)
Warning:
• Attach the electric component cover securely. If it is attached incorrectly, it
could result in a fire, electric shock due to dust, water, etc.
• Use the specified indoor/outdoor unit connecting cable to connect the indoor
and outdoor units and fix the cable to the terminal block securely so that no
stress is applied to the connecting section of the terminal block. Incomplete
connection or fixing of the cable could result in a fire.
G Drain pipe (O.D. ø32 PVC TUBE)
H Insulating material (purchased locally)
I Transparent PVC pipe
J O.D. ø32 PVC TUBE (Slope 1/100 or more)
K Band (small)
L Drain socket
Input capacity Main Switch/Fuse (A)
SLZ-KA25
SLZ-KA35
SLZ-KA50
10
10
20
7