Additional Venting Information
Do not mix and match components from different pipe manufacturers when assembling
your venting system (i.e. Do NOT use venting pipe from one manufacturer and a thimble
from another).
We require a minimum vertical rise of 36 in. (3 ft.) of pipe to create natural draft in the
system, which helps evacuate smoke from the stove in the event of a power failure or
combustion blower failure.
Venting systems 15.0 ft. or shorter may be composed entirely of 3.0 in. pellet pipe; to
reduce frictional losses, venting systems longer than 15.0 ft. should be composed of 4.0
in. pellet pipe.
Do not terminate the venting system directly beneath any combustible structure such as
a porch or deck.
Follow NFPA 211 rules listed below for venting system termination location relative to
windows and other openings in the dwelling.
o NFPA 211 (2006 ed.) Section 10.4 Termination: 10.4.5
(1) The exit terminal of a mechanical draft system other than direct vent
appliances (sealed combustion system appliances) shall be located in accordance
with the following:
Distance between the termination opening and grade should be a minimum of 2 ft. (24
in.) contingent on the grade surface below the termination. When determining the
termination height above grade, consider snow drift lines and combustibles such as
grass or leaf accumulation. In areas where significant snowfall is possible, the
termination height must be sufficiently high to keep the termination free of snow
accumulation.
Do not use makeshift compromises during installation or install any component of the
unit or venting system in such a manner that could result in a hazardous installation.
A chimney connector shall not pass through an attic or roof space, closet or similar
concealed space, or a floor, or ceiling.
Where passage through a wall or partition of combustible material is desired, the
installation shall conform to CAN/CSA‐B365.
Venting system surfaces get HOT, and can cause burns if touched. Noncombustible
IMPORTANT! READ AND FOLLOW ALL INSTALLATION AND MAINTENANCE INSTRUCTIONS, INCLUDING
CLEANING THE UNIT AS SPECIFIED, AND REPLACING GASKETS ANNUALLY, AND PARTS AS NEEDED.
ENGLAND'S STOVE WORKS IS NOT RESPONSIBLE FOR ANY DAMAGE OR INJURY INCURRED DUE TO NEGLECT, OR
DUE TO UNSAFE INSTALLATION OR USAGE OF THIS PRODUCT. CALL TECHNICAL SUPPORT WITH QUESTIONS.
(a) Not less than 3 ft. (.91 m) above any forced air inlet located within 10
ft. (3.0m).
(b) Not less than 4 ft. (1.2 m) below, 4 ft. (1.2 m) horizontally from or 1 ft.
(305 mm) above any door, window or gravity air inlet into any building.
(c) Not less than 2 ft. (0.61 m) from an adjacent building and not less than
7 ft. (2.1 m) above grade when located adjacent to public walkways.
shielding or guards may be required.
WARNING:
64