Vertical Installations
Always maintain a 1" clearance around the vent pipe (vertical) and 1" clearance horizontal, when passing through
ceilings, walls, roofs, enclosures, attic rafter or any combustible surfaces.
When passing through a flat ceiling install a Box/Wall thimble. Cut an 11" square hole and frame as shown in
the diagram below.
ALWAYS CHECK YOUR LOCAL CODES BEFORE INSTALLING VENTING. CLEARANCES ETC, MAY
TOUJOURS vérifier les codes locaux avant l'installation VENTILATION. ETC DÉGAGEMENTS, peut
CONSULT DURAVENT PARTS LIST OR INCA METAL CUTTING PARTS LIST FOR PART NUMBERS.
FOR SECURITY CHIMNEY, ICC AND METAL FAB CONTACT YOUR LOCAL SUPPLIER.
CONSULTEZ LA LISTE DES PIÈCES DURAVENT OU LA LISTE DES PIÈCES DE DÉCOUPE
MÉTALLIQUES INCA POUR LES NUMÉROS DE PIÈCES. POUR LA CHEMINÉE DE SÉCURITÉ, ICC ET
See section 3.3.4 Venting for instructions on how to connect Security or Dura-vent venting.
DO NOT PACK AIR SPACES WITH INSULATION
NE PAS PACK ESPACES D'AIR AVEC ISOLATION
11" x 11"
opening
VARY FROM STATE TO STATE (PROVINCE TO PROVINCE).
varier d'ÉTAT (PROVINCE).
METAL FAB, CONTACTEZ VOTRE FOURNISSEUR LOCAL.
Page 32 of 57