Minimum Clearances; Minimum Clearances To Combustibles - Inca Metal Cutting GALAXY Série Manuel D'installation Et Guide De L'utilisateur

Masquer les pouces Voir aussi pour GALAXY Série:
Table des Matières

Publicité

43.17
G
F
H
D
THERE CAN BE NO WEIGHT BEARING ONTO THE FIREPLACE.
ALL CONSTRUCTION ABOVE THE FIREPLACE MUST BE SELF SUPPORTING.
NO DRYWALL SCREWS INTO THE METAL OF THE FIREPLACE.
USE A HIGH TEMPERATURE SILICONE TO ADHERE TO THE METAL
A = 24"
MAXIMUM ALLOWABLE HEIGHT FROM FLOOR TO BOTTOM OF FIREPLACE
B = 1"
C = 19.57"
D = 18"
E = 36.52"
F = 1"
G=26.71"
H = 0"
I = 72"
3.3.2 MINIMUM CLEARANCES / DÉGAGEMENTS
F
41.27
A
FRAMING DIMENSIONS : 43.25'' W x 36.5'' H x 19.5'' D

MINIMUM CLEARANCES TO COMBUSTIBLES

IF BUILDING UP OFF THE FLOOR ON A PLATFORM
TO INTERNAL BACK COMBUSTIBLES
TO BACK WALL FROM FRONT OF UNIT
FROM EDGE OF FIREPLACE TO SIDE WALL
FROM BOTTOM OF FIREPLACE TO STUD
TO INTERNAL SIDE COMBUSTIBLES
MINIMUM FROM BOTTOM OF FIREPLACE TO MANTLE
(SEE DIAGRAMS NEXT PAGES)
11.34" FROM BASE OF SUPPORT CHANNELS AT BOTTOM OF UNIT
INTERNAL CEILING HEIGHT MINIMUM FROM BASE OF UNIT
I
E
B
C
Page 18 of 57