S+S Regeltechnik HYGRASGARD RPFF Série Notice D'instruction page 11

Masquer les pouces Voir aussi pour HYGRASGARD RPFF Série:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

G
®
HYGRASGARD
Quality product for HVAC sector, accuracy ± 2 % bzw. ± 3 % r. H.
The calibratable pendulum room humidity and temperature sensor HYGRASGARD
RPFF - 25 ⁄ RPFTF - 25 (± 2 %) with pluggable metal sinter filter; measures the relative humidity and temperature of air. It converts the measurands
humidity and temperature into standard signals of 0 - 10 V or 4...20 mA and is available with or without an optional display. It has four switchable
temperature ranges. Relative humidity (in % r. H.) is the quotient of water vapour partial pressure divided by the saturation vapour pressure at the
respective gas temperature. The sensor is applied in non-aggressive dust-free atmospheres in refrigeration, air conditioning, ventilation and clean
room technology, hotels, technical rooms, meeting rooms and convention centres. These measuring transducers are designed for exact detection of
temperature and humidity. A digital long-term stable sensor is used as a measuring element for humidity and temperature measurement. Fine
adjustment by the user is possible. The sensor is appropriate for ceiling and duct installation, or for integrating it into equipment.
TECHNISCHE DATEN
Power supply:
Power consumption:
Sensors:
Sensor protection:
HUMIDITY:
Measuring range, humidity:
Operating range, humidity:
Deviation, humidity:
Output, humidity:
TEMPERATURE:
Measuring range, temperature:
Operating range, temperature:
Deviation, temperature:
Output, temperature:
Ambient temperature:
Long-term stability:
Electrical connection:
Cable length:
Enclosure:
Enclosure dimensions:
Cable gland:
Protective tube:
Protection class:
Protection type:
Standards:
Optional:
RPFF ⁄ RPFTF (± 3 %), RPFF - 25 ⁄ RPFTF -25 (± 2 %)
24 V AC (± 20 %) and 15...36 V DC (± 10 %) for U variant
15...36 V DC (± 10 %) for I variant (depending on working resistance)
< 1.1 VA ⁄ 24 V DC ; < 2.2 VA ⁄ 24 V AC
digital humidity sensor with integrated temperature sensor,
low hysteresis, high long-term stability
RPFF ⁄ RPFTF:
RPFF - 25 ⁄ RPFTF - 25: metal sinter filter, Ø 16 mm, L = 88.5 mm,
0...100 % r. H. (output corresponding to 0 -10 V or 4...20 mA)
0...95 % r. H. (without formation of dew)
RPFF ⁄ RPFTF:
RPFF - 25 ⁄ RPFTF - 25: ± 2 % r. H. (20...80 %) at +20 °C, otherwise ± 5 % r. H.
0 - 10 V at U variant
4...20 mA at I variant, working resistance < 800 Ω,
see load resistance diagram
multi-range switching with 4 switchable measuring ranges (see table)
–35...+35 °C; –35...+75 °C; 0...+50 °C; 0...+80 °C
(output corresponding to 0 -10 V or 4...20 mA)
–35...+80 °C
± 0.5 K at +20 °C
0 -10 V or 4...20 mA
RPFF ⁄ RPFTF:
RPFF - 25 ⁄ RPFTF - 25: storage –35...+85 °C;
± 1 % per year
2-, 3-, or 4-wire connection (see connecting diagram),
0.14 - 1.5 mm² via terminal screws on circuit board
2 m, other lengths optional
plastic, material polyamide, 30 % glass-globe-reinforced,
with quick-locking screws (slotted ⁄ Phillips head combination),
colour traffic white (similar RAL 9016), enclosure cover for display is transparent !
RPFF ⁄ RPFTF:
RPFF - 25 ⁄ RPFTF - 25: 126 x 90 x 50 mm (Tyr 2)
M 16 x 1.5, including strain relief, exchangeable, max. inner diameter 10.4 mm
stainless steel,
RPFF ⁄ RPFTF:
RPFF - 25 ⁄ RPFTF - 25: Ø = 18 mm (16 mm), L = 120 mm
III (according to EN 60 730)
IP 65 (according to EN 60 529)
CE conformity,
according to EMC directive 2004 ⁄ 108 ⁄ EC,
according to EN 61326-1, according to EN 61326-2-3
display with iillumination, for displaying ACTUAL temperature and ⁄ or ACTUAL humidity
RPFF ⁄ RPFTF:
RPFF - 25 ⁄ RPFTF - 25: three-line, cutout approx. 70 x 40 mm (W x H), (Tyr 2)
®
plastic sinter filter, Ø 16 mm, L = 35 mm, exchangeable
(optional metal sinter filter, Ø 16 mm, L = 32 mm)
with exchangeable, pluggable measuring head (probe)
± 3 % r. H. (20...80 %) at +20 °C, otherwise ± 5 % r. H
storage –5...+60 °C;
operation –5...+60 °C
operation –30...+70 °C
72 x 64 x 37,8 mm (Tyr 1 without display)
72 x 64 x 43,3 mm (Tyr 1 with display)
Ø =16 mm, L = 142 mm
two-line, cutout approx. 36 x15 mm (W x H), (Tyr 1)
11
RPFF ⁄ RPFTF (± 3 % ) with plastic sinter filter or
3% = Rev. 2016 - V12 GB
2% =Rev. 2016 - V22 GB

Publicité

Table des Matières
loading

Table des Matières