Installation Of Pmv Kit; Refrigerant Piping - Toshiba PMV Kit RBM-PMV0363E Manuel D'installation

Masquer les pouces Voir aussi pour PMV Kit RBM-PMV0363E:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 11
4

INSTALLATION OF PMV KIT

Install the unit securely in the place to sufficiently withstand the weight of the unit.
If the foundation is not sturdy enough, the unit may fall and cause personal injury.
Perform a specified installation work to guard against earthquake.
Improper installation may cause the unit to fall.
REQUIREMENT
To prevent damage on the PMV Kit or personal injury, follow the instructions below.
• Do not step, or put any heavy object on the packed PMV Kit.
• When carrying the PMV Kit, hold the two hanging brackets and be careful not to apply excessive force to
the refrigerant pipes.
External view
Refrigerant pipe connecting port
(Liquid pipe)
58
55
30
NO GOOD
OK
PMV Kit
Indoor unit
Indoor unit
EN-7
WARNING
Refrigerant pipe connecting port
(Liquid pipe)
226
55
Connection cable
(accessory)
Note)
Do not connect two or more indoor units to one
PMV Kit.
PMV Kit
Arrange one indoor unit and one PMV Kit set to 1
by 1.
5

REFRIGERANT PIPING

If refrigerant gas has leaked during the installation work, ventilate the room immediately.
If the leaked refrigerant gas comes in contact with fire, noxious gas may be generated.
After the installation work, confirm that refrigerant gas does not leak.
If refrigerant gas leaks into the room and flows near a fire source, such as a fan heater, cooking stove or
heating unit, noxious gas may be generated.
Allowable length of refrigerant piping
The straight pipe section should be at least 0.2 m as shown in the figure below.
∗ Short length of the straight pipe section may cause abnormal sounds.
0.2 m or more
2 m to 10 m
PMV Kit
Refrigerant pipe
• Connecting direction of refrigerant pipe
When connecting pipes, be careful of direction of the
main unit.
Be sure to install the main unit so that
[
] mark in the label directs upward.
For connection of the refrigerant pipes, follow the arrow
mark in the label and connect pipes after confirming
directions of indoor unit and outdoor unit.
30
Piping material and dimensions
26
Model name
Indoor unit capacity type
RBM-PMV0363E
005, 007, 009, 012 type
015, 018 type
RBM-PMV0903E
024, 027 type
When connecting Ø9.5 refrigerant pipes, be sure to insert a seal pipe between PMV main unit and the joint.
If the seal pipe is not inserted, refrigerant leakage is caused.
PMV Kit
Seal pipe
Attached joint
5
WARNING
Indoor unit
Label
Diameter of refrigerant pipe
Notes
Ø6.4
Ø6.4
Attached joint
Ø9.5
CAUTION
Attached joint
Liquid pipe
EN
Attached joint
EN-8

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Pmv kit rbm-pmv0903e

Table des Matières