3

SELECTION OF INSTALLATION PLACE

Do not install the air conditioner at place where combustible gas may leak.
If gas leaks and is collected at surrounding the unit, the production of fire may be caused.
Upon customer's approval, install the air conditioner at a place where satisfies the following
conditions.
• Place where it can be installed horizontally.
• Place which can reserve a service space for safe maintenance or check.
• Place where there is no problem even if the drained water flows.
Apply electric insulation between metal section of the building and metal section of the air
conditioner in conformance with the Local Regulation.
Avoid the following places.
• Salty place (seaside area) or place with much gas sulfide (hot spring area)
(If selecting such a place, a special maintenance is required.)
• Place where oil (including machine oil), steam, oil smoke or corrosive gas generates.
• Place where a device generating high frequency (inverter, non-utility generator, medical apparatus, or
communication equipment) is set.
(A bad influence may generate by malfunction of the air conditioner, control error, or noise for such
equipment.)
EN-5
CAUTION
4
Installation space
• Make space for installation and service. (Make space to the electrical parts box cover side for service.)
• When installing the unit inside the ceiling, be sure to create a check port.
The check port is required when the unit is installed and serviced. (Check port: 450 × 450 or more)
• Keep a clearance of 50 mm or more between the top panel of the unit and the ceiling.
• The length of a connection pipe to the indoor unit should be 2 m to 10 m.
Installation space
RBM-PMV0363E, RBM-PMV0903E
55
55
200 or more
200 or more
RBM-PMV0903E (When attached joint is used)
73
73
200 or more
200 or more
EN
Box cover
Check port
450 × 450
EN-6