Daikin UATYQ250MCY17 Manuel D'installation page 28

Conditionneurs d'air en toiture
Table des Matières

Publicité

Shunt jumper 1, 2 and 3: Minimum fresh air opening setting in fan mode, where by the selection of different pins
will give different opening setting. Let name the shunt jumper 1 = JP1, shunt jumper 2 = JP2 and shunt jumper 3
= JP3; refer the table below for different fresh air opening selection:-
Fresh air opening (%)
0 (default)
10
20
30
40
50
70
85
Legend: OFF = Short pin 2 and pin 3
ON = Short pin 1 and pin 2
Dip Switch 1, 2 and 3 allow only 1 pin selection. Multiple pins selection will cause error and the operation will go back to
default setting. While Dip Switch 4 allow multiple pins selection.
Location of dip switches and shunt jumpers
in the economizer controller board:
Shunt jumper 2
Shunt jumper 1
Dip Switch 1
Dip Switch 2
ü
There are two LEDs in economizer controller board, which are green LED and red LED. Green LED will blink when
economizer controller board is powered-up. Red LED will blink when error(s) occur. Refer the table below for
error codes and their meaning:-
Error
Fault
Code
F0
Fresh air actuator faulty/ malfunction
F1
Return air actuator faulty/ malfunction
F2
Communication error
F3
CO
2
F4
CO
2
F5
Fresh air RH sensor short
F6
Fresh air RH sensor open
F7
Return air RH sensor short
F8
Return air RH sensor open
F9
Activation of actuator protection
FA
Multiple pins selection in Dip Switch 1, 2 or 3
When error(s) occur and the faults persist, please call your authorized local dealer/ serviceman for
troubleshooting. However, all the errors occur in economizer controller board will not affect the normal
operation of rooftop unit.
26
JP1
OFF
OFF
OFF
OFF
ON
ON
ON
ON
Shunt jumper 3
Dip Switch 3
Dip Switch 4
sensor short
sensor open
JP2
JP3
OFF
OFF
OFF
ON
ON
OFF
ON
ON
OFF
OFF
OFF
ON
ON
OFF
ON
ON
CAUTION
Indication on the economizer controller board:
Indication for the means of selection for shunt
Indication for the
means of selection
for Dip Switch 1.
Indication for the
means of selection
for Dip Switch 2.
The error codes will be shown on the seven segment
display on the economizer controller board.
jumper 1, 2 and 3.
Indication for the
means of selection
for Dip Switch 3.
Indication for the
means of selection
for Dip Switch 4.
Seven segment display