aldes Dee Fly Cube 550+ Notice D'installation page 113

Table des Matières

Publicité

Ti (in)max
This parameter is available if the control is set to run an electric post-heating system or a modulated water-based
heating/cooling system.
28
32
Valv.sec.
This parameter is available if the control is set to run a modulated water-based post heating/cooling system.
60
600
Pir min.
This parameter is available if one digital input is configured at the PIR value (presence detector, see Factory menu).
001
240 Default value 10, it is expressed in minutes; it is the time during which the fans run at the maximum
Boost min.
This parameter is available if one digital input is configured at the booster value (Factory menu)
001
240 Default value 10, is expressed in minutes; after the pulse from an external contact (closing of a NO
Default value 30, it is expressed in degrees centigrade; it is the maximum value of the range in which
the control keeps the temperature of the supply air flow in heating or cooling mode (see parameters
Ti (in)min, Ti min inv. and Ti min est.).
Default value 120, it is expressed in seconds; it indicates the opening/closing time of the solenoid
valve 3 èpoints, it is adjustable in 10-second steps.
speed after the pulse (closing of a NO contact) from a presence detector. After this lapse, the fans
will return to run at the speed set from the control panel until the pulse from the presence detector
is lost; since now on, the fans will run at the minimum speed.
contact) the fans run at the maximum speed (booster). When the pulse from the external contact
is lost (external contact open), the fans keep running at the maximum speed for the time fixed by
this parameter. When the booster function is off, the fans run at the speed set on the control panel.
113

Publicité

Table des Matières
loading

Table des Matières