aldes Dee Fly Cube 550+ Notice D'installation page 112

Table des Matières

Publicité

0.40
Tau Dp sec.
This parameter is only available for constant pressure units with control on one flow (Factory menu).
030
Max Flow
This parameter is only available for units with constant pressure (Factory menu).
20000 m3\h
Flow Exhau.
This parameter is only available for units with constant pressure with control on both flows (Factory menu).
= XXX%
Flow supply
074%
135%
Kp Flow Sup This parameter is only available for constant flow units with control on both flows (Factory menu).
0.40
Tau Flow
This parameter is only available for constant flow units with control on both flows (Factory menu).
Su s
030
Kp Flow Exh This parameter is only available for constant flow units with control on both flows (Factory menu).
0.40
Tau Flow
This parameter is only available for constant flow units with control on both flows (Factory menu).
EX s
030
Kp Flow
This parameter is only available for constant pressure units with control on one flow (Factory menu).
0.40
Tau Flow sec This parameter is only available for constant pressure units with control on one flow (Factory menu).
030
Adjust zero
Le capteur de pression peut être réinitialisé grâce à ce paramètre.
Dp/Flow
Cette opération doit s'exécuter quand le système est éteint, il est également préférable d'effectuer cette démarche
de manière régulière afin de corriger toute erreur de lecture.
Fan exhau.=
This parameter is available if the control is set to run variable speed fans (Factory menu).
XXX%
Fan supply
074%
135%
Ti (in)min
This parameter is available if the control is set to run an electric or modulated water-based after heating system
(no water-based cooling).
16
20
Ti min inv.
This parameter is available if the control is set to run a modulated water-based air after-treatment system.
16
20
Ti min est.
This parameter is available if the control is set to run a modulated water-based air after-treatment system (heating/
cooling).
20
24
It is the value of the proportional coefficient relevant to the detected flow.
It is the value of the integral time relevant to the detected flow.
Default value 100%, expresses, as a percentage, the desired ratio between the exhaust fan flow
and the supply fan flow, which creates an imbalance between the flows of both flows.
It is the value of the proportional coefficient relevant to the input flow.
It is the value of the integral time relevant to the input flow.
It is the value of the proportional coefficient relevant to the return flow.
It is the value of the integral time relevant to the return flow.
It is the value of the proportional coefficient relevant to the detected flow.
It is the value of the integral time relevant to the detected flow.
Default value 100%, it expresses, in a percentage format, the desired ratio between the exhaust fan
speed and the input fan speed that generates an imbalance between the air flows.
The maximum speed that can be set in the main window will always be 100%, what changes is the
minimum speed value that can be set by the final user (see Max. speed).
Default value 18, it is expressed in degrees centigrade; it is the minimum value of the range in which
the control keeps the temperature of the supply air flow
Default value 18, it is expressed in degrees centigrade; it is the minimum value of the range in which
the control keeps the temperature of the supply air flow in heating mode (Parameters menu, Winter
season):
Default value 22, it is expressed in degrees centigrade; it is the minimum value of the range in
which the control keeps the temperature of the supply air flow in cooling mode (Parameters menu,
Summer season):
TI [(TI (in)min est. TI (in)max)]
112