7.3 Faults and their rectification
RB-ZF4 room air control
Always call on the services of a
specialist installer if the error
message continues to appear after
a fault has been acknowledged.
For the fault rectification, cancel
fault message on the RB-ZF4
Chapter 7.2.1.
Fault on
RB-ZF4
Fans not opera-
ting. All 3 LEDs
on the RB-ZF4
flash.
Fans not opera-
ting. All 3 LEDs
on the RB-ZF4
flash.
Possible cause
No supply voltage
to the fans.
Control circuit board
faulty.
Fan defective
Check
Measure supply voltage
of supply air and exhaust
air fan.
(Terminal
and
(exhaust air/supply air) on
control circuit board A2).
Supply air or exhaust air
defined voltage at the
plug pins < 1.7 V.
Before the measure-
ment, cancel fault
message as described
in Chapter 7.2.1.
Measure the supply air
and exhaust
air defined voltage
(1.7...10 V DC).
Supply air and exhaust
air defined voltage
at plug pins of 1.7...10 V
(value depends on the
set ventilation level).
7. Faults, messages │ uk
Rectification
Press the ²
button for
about 5 seconds.
If the fault is not rectified,
the fault message
appears again after
about 1 minute. If this
happens, replace the
control circuit board.
Replace control circuit
board.
Correct jumper settings.
Should the fault occur
again, replace exhaust
air or supply air fan.
33