G
FSTM ⁄ FSTM-P | FSFM ⁄ FSFTM | FSCO
The room sensor THERMASGARD
is used for measuring the room temperature, and for setpoint adjustment.
The room sensor HYGRASGARD
is used for measuring the relative humidity and temperature of the air.
The room sensor AERASGARD
is used for measuring the CO
2
A digital, long-term stable sensor is used for humidity and temperature measurement. Relative humidity [% r. H.] is the quotient of water vapour
partial pressure divided by the saturation vapour pressure at the respective gas temperature. The CO
optical NDIR sensor (non-dispersive infra-red technology). The measuring transducer converts the measured values into a standard signal of 0 - 10 V.
The in-wall sensor is mounted in high-quality panel switch programmes, ideally of the brands Gira, Berker, Merten, Jung, Siemens or Busch-Jaeger
(using in-wall adapters, no setpoint adjustment possible) either individually or in combination with light switches, socket outlets, etc. It is used in
non-aggressive, dust-free environments, in refrigeration, air conditioning and clean room technology, and in interior rooms, such as living rooms,
offices, hotels, etc.
TECHNICAL DATA
Power supply:
Power consumption:
HUMIDIT Y
Sensor:
Long-term stability:
Measuring range, humidity::
Operating range, humidity:
Deviation, humidity:
Output, humidity:
TEMPERATURE
Measuring range:
Deviation, temperature:
Output, temperature:
Output, potentiometer:
CARBON DIOXIDE (CO
)
2
Sensor, CO
:
2
Long-term stability:
Measuring range, CO
:
2
Output, CO
:
2
Measuring accuracy, CO
:
2
Temperature dependence, CO
:
2
Pressure dependence:
Gas exchange:
Warm up time:
Response time:
Mounting:
Electrical connection:
Ambient temperature:
Permitted humidity:
Medium:
Protection class:
Protection type:
Standards:
S W I T C H P R O G R A MME
Manufacturer:
Housing:
FSTM ⁄ FSTM - P in the in-wall enclosure, optionally with potentiometer,
®
FSFM ⁄ FSFTM in the in-wall enclosure
®
FSCO
⁄ FSTM - CO
®
in the in-wall enclosure
2
2
content and temperature of the air.
24 V AC ⁄ DC (± 10 %)
< 1.1 W ⁄ 24 V DC ; < 2.2 VA ⁄ 24 V AC (FSTM ⁄ FSTM-P ⁄ FSFM ⁄ FSFTM)
< 1.5 W ⁄ 24 V DC ; < 2.9 VA ⁄ 24 V AC (FSCO
digital humidity sensor with integrated temperature sensor,
low hysteresis, high long-term stability
± 1 % per year
0...100 % r. H.
0...95 % r. H. (non-precipitating air)
typically ± 3.0 % (20...80 % r. H.) at +25 °C, otherwise ± 5.0 %
0 - 10 V
0...+50 °C
typically ± 0.8 K at +25 °C
0 - 10 V
0 - 10 V (FSTM-P with setpoint adjustment, not possible with Busch-Jaeger)
optical NDIR sensor (non-dispersive infra-red technology),
with manual calibration (via zero button) and automatic calibration (fixed)
< 2 % in 15 years
0...2000 ppm
0 - 10 V
typically ± 30 ppm ± 3 % of measured value
± 5 ppm ⁄ °C or ± 0.5 % of measured value ⁄ °C (whichever is higher)
± 0.13 % ⁄ mm Hg
by diffusion
approx. 1 hour
< 2 minutes
in-wall flush box Ø 55 mm
0.14 - 1.5 mm², via screw terminals
Storage –35...+85 °C; Operation 0...+50 °C
max. 90 % r.H., non-precipitating air
clean air and other non-aggressive, non-combustible gases
III (according to EN 60 730)
IP 20 (according to 60 529)
CE-conformity, electromagnetic compatibility according to EN 61 326, EMC Directive 2014 ⁄ 30 ⁄ EU
GIRA System 55
(other switch programmes, manufacturers, colours as well as prices available upon request)
plastic, the standard colour is pure glossy white (similar to RAL 9010)
(other colours are available upon request with colour variants depending on the respective light switch programme)
⁄ FSTM-CO
2
2
⁄ FSTM-CO
2
2
10
content of the air is measured using an
2
)
Rev. 2019 - V11