The charger should be placed as close as possible to the
battery, but always in a separate box. The box for the battery
must have a ventilation hole facing towards the outside.
Attach the device securely with the four fastening screws
supplied.
Important
Make sure that the ventilation slots remain unobstructed! The
minimum clear distance must be 100 mm all around! Insuffi-
cient ventilation can cause overheating of the device!
The device is designed for operation in ambient temperatures
of up to 35 °C. If the temperature inside the device rises due
to a lack of air circulation or due to high ambient temperature,
the charging current is automatically reduced in steps.
Handling of the cage tension spring
clamps
Prepare the connection cables. The cable end to be connected
to terminal B+ (small caged spring terminal) must be stripped
over a length of 8 – 9 mm. The cable ends for the battery con-
nections (large cage tension spring clamps) must be stripped
11 – 12 mm. Cable end sleeves are not required.
The spring terminal can be opened up with the aid of a suit-
able slit screwdriver.
Insert the tip of the screwdriver into the upper, square open-
ing, and push on the spring terminal. The spring terminal in
the lower, round opening opens up.
Insert the cable into the spring terminal as far as the insula-
tion (lower, round opening) and remove the screwdriver. The
tension spring clamp closes again and the cable is securely
clamped.
Repeat the procedure for all connections:
B+ Sense, + Batt. I, + Batt. II, - Batt. I, - Batt. II.
Make sure that the cable ends sit firmly in the cage tension
spring clamps!
21