STUDER Innotec
3.3
Connections
3.3.1 General instructions on connecting
The cable connection on the terminals AC INPUT / AC OUTPUT / 16A 230VAC
are carried out with a screwdriver Nr.1 and the connection on the SOLAR
terminal with a screwdriver Nr.2.
The conductor cross section on the terminals AC INPUT / AC OUTPUT / 16A
230VAC of the connecting cable must be minimum 2.5mm2.
All connecting cables and also the mounted battery cables, must be fixed with
strain relief clamps.
The COMPACT is delivered with battery cables already connected.
The battery cables must never be extended. If the extension is unavoidable then
the conductor cross section must be elevated accordingly.
To protect the battery cable, a fuse corresponding to the conductor cross
section must be fixed directly on to the battery.
All cables must be tightly screwed in place. For safety, a yearly control is
recommended. In mobile installations control must be carried out more often.
Connecting must be done by qualified personnel. Material such as cable,
connectors and distribution boxes, fuses etc. used in the installation must
comply with the respective valid low-voltage installation rules and regulations.
3.3.2 Protection cover of the terminals connections
The protection is available as an option (Order ref.
CFC-01) to avoid to do accidental and hazardous
contact on the terminals 230Vac if the unit is monted
in a non restricted area. It mounted with strain relief
clamps for the cable.