5_ when the gate has closed, after approximately 2 seconds a complete opening manoeuvre is ex-
ecuted automatically;
6_ when the gate has opened, wait for the DL3 led to be fixedly on, then set dip-switch no.10 to OFF;
7_ the automation is now ready for operation.
Make the logic adjustments.
When any adjusting devices (trimmers or dip-switches) on the control panel are oper-
ated, a complete manoeuvre must be carried out in order for the new settings to take
effect.
6. LOGIC ADJUSTMENTS
TRIMMER
RALL.
Deceleration adjustment: from 50 to 120 cm before the limit switch;
Note: the automation must perform a complete opening and closing manoeuvre be-
fore setting the deceleration.
FR.
Obstacle detection sensitivity adjustment. The trimmer is set to provide sufficient thrust to
work the gate without exceeding the limits established by current standards (EN 12453).
Turning the trimmer clockwise (+) increases the motor torque, turning it anticlockwise (-)
reduces it.
T.C.A.
Automatic Closing time adjustment: from about 3 to 255 seconds (see dip-switch no. 1);
witch
Dip s
AUTOMATIC
1
CLOSING
2
2 / 4 STROKE
OPENING
3
PHOTOCELLS
OPERATION
4
NO REVERSE
PRE-
5
FLASHING
PHOTOCELL
6
TEST
2nd RADIO CHAN-
7
NEL OPERATION
MEMORIZATION
8
SPEED / DECELERA-
TION
SENSITIVE
9
EDGE
after opening, the gate automatically closes when the delay set on the
On
T.C.A. trimmer expires.
Off
automatic closing disabled.
with automatic closing enabled, a sequence of open/close commands
On
causes the gate to OPEN-CLOSE-OPEN-CLOSE etc (see also dip switch
4).
in the same conditions, the same command sequence causes the gate
Off
to OPEN-STOP-CLOSE-STOP-OPEN-STOP (step-by-step).
during opening, the photocell cuts in to stop the gate until the obstacle
On
is removed. When the obstacle is removed the gate resumes opening;
Off
during opening, the photocell does not cut in.
the open-close pushbutton reverses the direction of movement of the
On
gate even while it is opening.
NO-REVERSE function activated; the gate ignores the closure commands
Off
during opening and reversal of movement occurs only during closure;
On
the pre-flashing function enabled.
Off
the pre-flashing function disabled.
On
the "photocell test" function is enabled;
the "photocell test" function is disabled.
Off
Note: to be used when the photocells are not used.
Monostable function active for 2 sec.: the radio control impulse causes
On
the contact to activate and remain active for 2 sec.
Gate contact open: The contact activates on opening the gate and re-
Off
mains active during the open time, during the TCA and during reclo-
sure. It deactivates once the gate has completed its closure movement.
Increased speed value during the memorization / deceleration phase
On
for gates with sliding problems during opening / closing.
Normal speed value during the memorization / deceleration phase for
Off
gates without sliding problems during opening / closing.
On
RESISTIVE SENSITIVE EDGE (terminal no. 1);
Off
FIXED EDGE (NC contact – terminal no. 1);