CEILING ASSEMBLY
Ceiling mounting
The accessories needed for fitting the casings and condensate evacuation are supplied with the unit as standard:
• Mounting brackets
• Anti-vibration mounts are used to separate the motor from the ceiling to limit the transmission of noise.
• Condensation water drain nozzle
• Option: ceiling suspension kit including 4 threaded rods, washers and wall plugs. Plan for one kit per casing
(code 11023117)
• Drill a hole in the concrete tile as indicated on the diagram opposite
• Insert adequate wall plugs
• Screw in the 4 threaded rods (Ø 8 mm)
• Assemble the anti-vibration mountings
• Suspend the equipment in place
• Screw the condensation water drain nozzle into the exchanger
• Glue the bend to the white part
• Assemble the water trap to the bend. This water trap runs without any water.
Be carreful to the direction (arrow)
• The water trap need to be impervious, and not at the atmospheric pressure
Prohibited assemblies
620
27
Be careful that the direction
of the exchanger and motor are
correct! Whether in an assembled
or dissociated configuration,
the exchanger and motor must
always be in the same position
to each other.