7. Transporting the unit

[Fig. 7.0.1]
1 P72, P96
Slings
(Min. 8 m [26 ft.] x 2)
50 mm [1-31/32 in.] or
thicker protective pads
(two each in the front
and back)
Protective pads
(two each in the
front and back)
2 P120, P144
Slings
(Min. 8m [26 ft.] x 2)
50 mm [1-31/32 in.] or
thicker protective pads
(two each in the front
and back)
Protective pads
(two each in the
front and back)
Sling holes
(two each in the front and back)
• Use suspension ropes that will withstand the weight of the unit.
• When moving the unit, use a 4-point suspension, and avoid giving impacts to the unit (Do not use 2-point suspension).
• Place protective pads on the unit where it comes in contact with the ropes to protect the unit from being scratched.
• Use a 50 mm [1-31/32 in.] or thicker cardboard or cloth as a protective pad on the top of the unit to prevent contact between the fan guard and slings.
• Set the angle of roping at 40˚ or less.
• Use 2 ropes that are each longer than 8 m [26 ft].
Caution:
Be very careful when carrying/moving the product.
- When installing the outdoor unit, suspend the unit at the specified location of the unit base. Stabilize as necessary so that it does not move to the side and support it at
4 points. If the unit is installed or suspended with 3-point support, the unit may become unstable and fall.
8
40°
Fan guard
Sling holes
(two each in the front and back)
40°
Fan guard