G
THERMASGARD
®
Function 04 Read Input Register
Register
3x0001
Temperature
3x0002
Temperature
3x0003
Temperature
Function 02 Read Discrete Input
Register
0x0001
0x0002
Note: The addresses 1x0003...1x0008 are read with the value "0".
Function 08 Diagnostics
The following sub function codes are supported
Sub Function
Parameter
Code
Echo of transmission data
00
(Loopback)
Restart Modbus
01
(Reset listen-only mode)
04
Activation listen-only mode
10
Delete counter
11
Counter bus telegrams
Counter communication errors
12
(Parity, CRC, frame errors, etc.)
13
Counter exception telegrams
14
Counter slave telegrams
15
Counter telegrams without answer
Function 17 Report Slave ID
Composition of answer telegram
Byte No.
Parameter
00
Number of bytes
01
Slave ID (device type)
02
Slave ID (device class)
03
Status
04
Version number (release)
05
Version number (version)
06
Version number (index)
MODBUS | Telegrams
Parameter
Without filtering
1 sec. filtering
10 sec. filtering
Parameter
Sensor error – breakage
Sensor error – short circuit
Data Type
Value
Signed 16 Bit
– 500...+ 1500
– 999...+ 9999
Signed 16 Bit
– 500...+ 1500
– 999...+ 9999
Signed 16 Bit
– 500...+ 1500
– 999...+ 9999
Data Type
Value
Bit 0
0 / 1
Bit 1
0 / 1
Data Type
Answer
Echo data
Echo telegram
No answer
Echo telegram
Unsigned 16 Bit
All valid bus telegrams
Unsigned 16 Bit
Faulty bus telegrams
Unsigned 16 Bit
Error counter
Unsigned 16 Bit
Slave telegrams
Unsigned 16 Bit
Broadcast messages (address 0)
Data Type
Answer
Unsigned 8 Bit
6
Unsigned 8 Bit
2 = THERMASGARD
Unsigned 8 Bit
10 = THERMASGARD
Unsigned 8 Bit
255 = RUN, 0 = STOP
Unsigned 8 Bit
1...9
Unsigned 8 Bit
1...99
Unsigned 8 Bit
1
14
Range
– 50 ... +150 °C
Overflow
– 50 ... +150 °C
Overflow
– 50 ... +150 °C
Overflow
Range
ON - OFF
ON - OFF
®
MODBUS
®
/ THERMASREG
®